| |
|
 |
|
 |
|
|
|

|
The CorrView
® monitor offers significant advantages to any property
manager or plant operator by providing a more realistic estimate of actual
corrosion activity, as well as by allowing far more extensive monitoring
coverage. It also provides a benefit to those water treatment professionals
dedicated to providing the highest level of service to their clients.
The major advantage of CorrView
®, of course, is its fundamentally simple, low cost, and
maintenance free design. Of its many features, the fact that it is a totally
self contained corrosion monitoring device, and simple to install virtually
anywhere, extends the option of corrosion monitoring to important areas never
before possible, nor even considered. Read about some of
CorrView's ® advantages.

CorrView
® is a new product - having recently been awarded a United
States Patent. It was specifically invented in response to the high incidence
of corrosion produced piping failures seen at many New York City high rise
office buildings and elsewhere. The major purpose in its design was to produce
a simple and low cost method of better corrosion monitoring; one which, by
definition of its simplicity, would extend an awareness of common corrosion
problems and save valuable equipment and
expense.
While such corrosion problems
are, in most cases, produced due to a lack of adequate water treatment
protection, they are often unnecessarily allowed to develop into more serious
forms due to inaccurate monitoring methods, or a total lack thereof. Years of
performing ultrasonic piping investigations has allowed CorrView International
to document the fact that by the time most problems are finally discovered,
substantial damage has already taken place.

While various
other methods such as ultrasonic testing, linear polarization resistance, spool
pieces, corrosion coupons, and metallurgical sampling do offer excellent
testing options, only CorrView ® offers a cost effective
and long term monitoring solution for many applications.
The below listing offers
some suggested applications for CorrView ®, and
highlights specific problem areas within each application. Further detail for
the most common applications, and recommendations on its use, is available at
the above navigation bar.
We raise these
areas of concern based upon our 25 years of experience providing chemical water
treatment and ultrasonic pipe testing at some of the largest New York City
building properties, and elsewhere throughout the United States.
See Technical Bulletin
# C-10 regarding some common corrosion trends.
|

|
|
This is the number one problem area for most building owners
and plant managers due to the many aggressive forces at work. Condenser or open
water systems suffer from the combined effects of an inherently higher
corrosion rate, a totally oxygenated environment, airborne particulates,
sunlight, and a constant microbiological loading.
Further compounding
the problem is more corrosion susceptible steel, less effective chemical and
microbiological inhibitors, less tolerant engineering design, and greater
operating demands. Together, this often produces higher than acceptable
corrosion rates and deep pitting damage which may vary greatly according to the
location within the piping system.
The following areas traditionally
show higher corrosion activity, and are all recommended for closer
monitoring:
- By-pass lines
- Long horizontal runs
- Roof level piping
- HVAC units which may be shut
down
- Drained lines
- Dead end areas
- Smaller run-out piping to HVAC
units
- Lowest floor piping
- Low flow areas
- Return lines
- Mud legs or dead legs
- Small diameter threaded
pipe
- Alternating equipment
piping
- Future lines
- Terminated or abandoned piping

|
|

|
|
Chill water piping can usually be found having a low to
moderate corrosion rate. Only under unusual circumstances are problems ever
found at its interior.
A common source of high corrosion rates often
exist in colder climates where exposed coils are freeze protected over the
winter season using glycol. In addition to the partial draining of the pipe,
glycol offers an abundant food source to any microorganisms present, and can
create a serious MIC condition if allowed to continue. Regular chemical
cleanouts and sterilizations are advised in such cases.
Also a common
problem in colder climates is the direct connection of condenser water and
chill water lines to provide free cooling. In all examples, the strainers allow
substantial dirt and debris to enter and then settle into the closed system.
All microorganisms will easily pass through the filter as well. Problems
therefore develop at the lower floors and at long horizontal runs. Plate and
frame heat exchangers are clearly preferred as a free cooling
method.
Even under the best corrosion conditions, chill water systems
will still produce a substantial volume of rust deposits over many years. This
corrosion product accumulates to produce a heat transfer loss, and in the worst
cases - under deposit corrosion in areas where the iron oxide deposit settles.
View a table of rust
volume created for various corrosion rates.
While not
possible to actually monitor except visually, cold water piping also suffers
from the effects of external corrosion attack due to the failure to adequately
insulate the pipe from the migration of area moisture onto its cold surface. In
many examples, wall loss occurring due to external moisture condensation will
far outweigh that at the pipe's interior surface.
The following areas
traditionally show slightly higher corrosion activity, and are recommended for
closer monitoring:
- By-pass lines
- Long horizontal runs
- Drained lines
- Dead end areas
- Run-out piping to HVAC
units
- Lowest floor piping
- Mud legs or dead legs
- Small diameter threaded
pipe
- Alternating equipment
piping
- Future lines
- Terminated piping

|
|

|
|
Most closed systems operate under
relatively low corrosion conditions. This usually begins to accelerate after 10
or more years of service with the accumulation of interior deposits. Hot water
systems traditionally corrode at under 0.5 MPY, other closed and secondary
systems at near 1 MPY.
A failure to chemically clean a closed system
every five years and provide side stream filtration is often cited as the
reason for a corrosion problem. Microbiological contamination is less likely to
exist than for an open condenser water system, but always possible.
See Technical Bulletin
# W-1 regarding the use of side stream filtration to maintain clean closed
systems.
The same areas of concern for a chill water system
also exist for most closed systems, and the following are recommended for
closer monitoring:
- By-pass lines
- Long horizontal runs
- Drained lines
- Dead end areas
- Run-out piping to HVAC
units
- Lowest floor piping
- Mud legs or dead legs
- Small diameter threaded
pipe
- Alternating equipment
piping
- Future lines
- Terminated and abandoned piping

|
|

|
|
Fire sprinkler piping corrodes at a
rate generally dependent upon the amount of water flowing through it. For
systems where the pipe is left filled for decades, it is common to measure
perhaps 20 mils of total wall loss and no pitting. This is because a small
degree of corrosion takes place, the oxygen is depleted, and the corrosion
process virtually ceases.
Where a fire sprinkler system is extended and
modified, or constantly drained and filled, substantial wall loss can occur at
a rate similar to an untreated open water system. A small undetected leak at a
fire sprinkler system, because of the constant influx of fresh water, can
destroy the entire piping system in under 10 years.
Thin wall schedule
10 pipe, now commonly used for fire sprinkler service, is especially
susceptible to corrosion attack, and offers little available loss of wall
thickness before producing a leak. Most of the failures of sprinkler piping
systems we have seen have been primarily due to the use of schedule
10.
Preaction fire systems can suffer greatly due to their being
temporarily filled with water during hydrostatic testing and then drained. The
use of galvanized pipe does not offer a total solution, and such systems can
fail within a few years under certain conditions. Where the galvanized pipe is
not of top quality, the coating fails - producing accelerated under deposit
corrosion that can bore through pipe wall in as little as two years.
The following areas can exhibit higher corrosion activity, and can be
recommended for closer monitoring:
- Pipe having any water flow
activity
- Long horizontal runs
- Fire department test lines
- Frequently drained lines
- "Sweating" fire sprinkler
lines
- Preaction "dry"
piping
- Galvanized pipe
- Thin wall schedule 10 pipe

|
|

|
|
Domestic water problems are greatly
dependent upon the type of pipe material installed. Galvanized piping, which is
commonly used, suffers greatly once the galvanizing finish wears away and
random areas of under deposit corrosion develop. In extreme cases, deposits can
accumulate sufficiently to cause a water flow problem.
Deposits are
typically most severe at lower floor areas of the system and at horizontal
runs, but should be expected to exist throughout the system to some
degree.
Brass pipe is relatively unseen today except for older
properties. It corrodes very slowly and evenly than steel. Brass is more likely
to fail due to dezincification of the metal over decades, than due to a wall
loss problem caused by corrosion.
Copper pipe is increasingly used for
domestic water systems due to the recognized problems with galvanized pipe.
Except for aggressive local water, low pH conditions, microbiological activity,
or a cell induced corrosion problem, copper pipe will usually provide long
service life.
Only a galvanized steel domestic water line would warrant
corrosion monitoring. In such cases, some areas to consider would
be:
- Long horizontal runs
- Frequently drained lines
- Bottom of the piping system
- Thin wall schedule 10 pipe

|
|

|
|
Corrosion under insulation is a very
common problem generally dependant upon a combination of water temperature and
area humidity. In most cases, the fiberglass insulation applied is insufficient
to prevent the migration of moisture to the pipe - thereby opening a second
front for corrosion to attack the pipe. See Technical Bulletin
# P-6 for more about the threat of corrosion under
insulation.
While CorrView ® cannot
offer any benefit in this area, other technologies exist to "view" through the
insulation for such problem areas. No regular monitoring devices or methods
apply. Our best recommendation is to periodically remove sections of any cold
water pipe insulation in the following areas for visual inspection.
Supply side piping, extremely cold temperature services, and areas of
high humidity, especially where cold water pipe may run through a steam room,
for example, are high priority areas to check every few years. Protecting the
pipe with a high solids protective coating is always
recommended.
- High humidity areas
- Mechanical rooms
- Steam room areas
- High traffic areas
- Colder supply lines
- Horizontal lines
- Outdoor locations
- Areas of damaged insulation
- Brine or ammonia systems
|

Overall,
CorrView ® offers substantial benefits to anyone
responsible for HVAC or process piping systems. While not a single source
corrosion monitoring solution, its low cost and simple operation easily extends
its use into areas never before addressed. This, by definition, greatly
improves system reliability, as well as the chance of identifying a corrosion
problem before it becomes a major maintenance issue.
|
|
|
|
|
|
|

|

|
|
|
 |
|
|