| |
|
 |
|
 |
|
|
|

|
We offer below an
assortment of photographs taken from years of archived ultrasonic pipe testing
and remote visual inspection work. These graphically illustrate the various
forms of corrosion commonly found at HVAC cooling water and process piping
systems.
It can be virtually guaranteed
that some degree of certain corrosion types exist at every water circulating
system. But while corrosion itself cannot be totally prevented, it can be
controlled in order that problems do not reach the level of severity as shown
below.

|

|
|

|
Generalized Corrosion - This 40
year old sample of 8 in. schedule 80 pipe, while clearly containing deposits of
iron oxide, shows very even wall loss and long remaining service life.
The pipe was cleaned using high pressure water jet and returned to
service with approximately schedule 40 thickness remaining. |
|
Galvanic Corrosion -
An extremely common problem area due to the failure to install galvanic
insulators between carbon steel pipe and either brass valves or copper pipe.
Combined with schedule 40 pipe and a moderate corrosion rate, galvanic
corrosion will often produce premature failures with 6-10 years. |

|
 |
|
 |
Under Deposit Corrosion - A
condition often indicated ultrasonically by some areas showing at near original
specification, and adjacent areas of high wall loss.
It is more
prevalent at the bottom of horizontal lines, on lower floors, and where flow
rates are slowest. |
|
Total Thread Failure - A
potentially worst case scenario, this 1 in. take-off line from a 24 in. main
condenser water riser corroded completely through and separated.
Remarkably, corrosion product within the failed nipple held back 12
floors of water. |

|
 |
|
 |
Galvanic Corrosion - A combination
of water penetration through the roof level pipe insulation and galvanic
activity completely dissolved this pipe hanger.
Severe wall thickness
loss is obvious in the immediate area of the pipe hanger and resulted in the
need to replace this pipe. |
|
Galvanic Corrosion - Another
example of the higher corrosion activity usually existing at direct brass to
black iron connections.
At low corrosion rates, galvanic corrosion may
be negligible, but usually increases greatly once corrosion rates exceed 5
MPY. |

|

|
|
 |
Under Deposit Corrosion - Created
by either a corrosion cell or an MIC condition, high wall loss is typically
found under interior rust deposits - more commonly called tubercles.
Such localized and deep corrosion can easily reach rates of 25 MPY or
more, and destroy even larger diameter pipe in 5 years or less. |
|
Insulation / Galvanic - Moisture
penetrating through the insulation at this chill pipe provided an initiation to
an outer corrosion problem at the steel take-off line.
Exterior
moisture also assisted in the heavier attack at the threads due to galvanic
activity between brass valve and steel pipe. |

|

|
|
 |
Under Insulation Failure - The
general failure of this fiberglass chill water pipe insulation allowed moisture
to penetrate and produce severe pipe deterioration in localized areas.
Often seen as exempt from corrosion problems, this copper pipe was
severely pitted at its exterior and in need of replacement. |
|
CUI Corrosion - Often identified
only after the removal of pipe insulation for another purpose, water from rain
and snow typically penetrates most exterior installations to cause wide ranging
wall loss.
This creates a corrosion problem on two fronts, and can
produce severe damage over time. |

|

|
|
 |
Localized Pitting - Partially
water filled systems produce widely varying wall loss typically along the
bottom.
For this dry fire sprinkler system, testing showed virtually
new pipe after 25 years at the top, shown at the left. The wet pipe bottom
however, shown at the right, was totally deteriorated to the point of
failure. |
|
Under Deposit Corrosion - The
degree of wall loss occurring under tubercular deposits is generally
proportional to the volume or size of the internal deposit. A 0.100 in. wall
loss can translate into a 2 in. internal iron oxide deposit.
This photo
illustrates the greater threat of high wall loss over the restriction in water
flow. |

|

|
|
 |
CUI Corrosion - Roof level pipe
often suffers even higher exterior metal loss due to the combined effects of
moisture condensation, direct water infiltration, and insulation damage.
Such heavy deterioration is usually only discovered after a leak
occurs. |
|
Localized Corrosion - A good
example showing particulate deposits settling along the pipe bottom to produce
deep under deposit pitting.
Testing showed the side walls of the pipe
near factory specification, but total penetration of the pipe at the bottom and
lower sides. |

|

|
|

|
Galvanic Corrosion - Galvanic
corrosion is often suspected where the use of schedule 40 threaded pipe is
actually the basic problem.
While some additional wall loss might be
attributed to the attack of the brass valve upon the carbon steel, it is often
the 60% loss of pipe upon threading which will cause a premature leak.
|
|
Under Deposit Corrosion - The pipe
interior does not need to be completely covered with tubercular deposits to
produce a severe pitting condition.
Here, corrosion cells developed
randomly and widely spread along the bottom of this galvanized sprinkler pipe
to produce a total penetration of the pipe wall within 2 years. |

|

|
|

|
Pitting Corrosion - The presence
of one repair clamp and five nearby pinhole leaks confirms that a severe
corrosion problem exists at this fire sprinkler piping location.
This
is made worse by the original installation of thin wall schedule 10 stock,
where little wall thickness loss can be tolerated before reaching minimum
acceptable limits. |
|
MIC Corrosion - This photo of the
inside bottom of a cooling tower pan shows a severe and concentrated pitting
condition. The brown rust ring around each pinhole failure was a natural event
of the corrosion mechanism.
At the time that this photograph was taken,
MIC was the suspected cause of the filure, though not confirmed. |

|
 |
|
 |
CUI Corrosion - Similar to
interior corrosion, exterior pipe corrosion due to moisture condensation can
take the form of either deep and random pitting, or, as shown above - a
generalized deterioration of the entire surface.
Since iron oxide is
approximately 25 times less dense that the original steel, it often suggests a
much greater wall loss than actually exists. CUI is the greatest threat to
smaller diameter piping, but can severely reduce the service life of even the
largest sizes. |
|
Under Deposit Corrosion - Six pipe
clamps and three active leaks along this one single 18 ft. section of 6 in.
condenser water pipe suggested a severe corrosion problem. However no problems
were found elsewhere on the same system, and ultrasonic testing failed to
identify any significant wall loss.
The problem was identified as a
buildup of settled particulates in this by-pass line from supply to return, and
with the downstream side of the pipe closed only. |

|

|
|

|
Severe Pitting - An unexplained
pitting condition produced pinholes throughout this relatively new cooling
tower of only a few seasons in service.
Destructive analysis of failed
sections of the tower pan showed a combination of MIC and metallurgical defect
of the manufacture of the steel itself as producing this widespread problem.
|
|
Galvanized Pipe- Over 62 years of
carrying New York City domestic cold water in this 8 in. galvanized wrought
iron line produced this eventual result.
UT testing showed deep under
deposit pitting well throughout the pipe, and an overall corrosion rate of near
3.5 MPY. Corrosion produced both constricted smaller diameter pipe, and pinhole
failures. |

|

|
|

|
Heavy Deposits - A common
corrosion result following decades of fire standpipe service.
This
galvanized steel pipe is barely recognizable as such, and accumulated an
overall restriction of approximately 1 in. across this 6 in. diameter ID.
Concern was raised once pinhole failures started at the threaded joints, with
UT testing showing only 0.050 in. remaining in that area. |
|
Corrosion Under Insulation- High
humidity near an outdoor area, combined with a 42 º F chill water supply
temperature, thin 1 in. fiberglass, and no vapor barrier reduced the service
life of this area of piping to under 8 years.
This represented a
dramatic loss from other less affected areas of the same piping system - which
showed greater than 30 years of remaining life. |

|
 |
|
 |
Schedule 10 / Pitting - At least
15 pipe clamps over a single 21 ft. section of this 2-1/2 in. pipe suggested a
major corrosion problem. Ultrasonic testing, however, identified thin wall
schedule 10 sprinkler pipe used in some areas of this condenser water system.
In reality, the pipe had provided excellent service over its 18 year
history, and had simply reached the end of its useful service life. |
|
Pitting Corrosion - Deep pitting
typically shows itself first at the smaller diameter piping simply due to the
lower wall thickness present. Such evidence should be taken as an advance
indication that a system wide problem likely exists, rather than assumed a
localized event.
A failure at the midpoint of a pipe section suggests a
much greater corrosion problem than one at the threads. |

|
 |
|
 |
Roof Level Weathering - One of the
easiest corrosion problems to avoid but one of the most common, protecting this
pipe from external wall loss only requires some regular maintenance.
The addition of an unnecessary external corrosion condition will often
cut the estimated service life of the pipe in half, and produce unexpected
failure. Regular inspection and protective maintenance is required. |
|
Dezincification - Typical surface
deposit resulting from the dezincification of brass pipe due to old age and/or
an aggressive water condition.
Over many years, the zinc component of
the metal is leached out to leave copper. Deep pitting is initiated and the
pipe becomes porous prior to producing an actual leak, and leaving a corrosion
product behind. |

|
 |
|
 |
Galvanic Corrosion - An extremely
common problem for areas where brass or copper is joined to steel. Under
certain conditions, as shown here, it may also exist at steel to steel contact
points - where new pipe meets old, and where different ground potential
exists. |
|
CUI Corrosion - An extremely
common problem area in examples where very cold pipe temperatures and high
humidity combine under insufficient insulation protection.
CUI is a
greater threat to chill water supply pipe than normal internal corrosion
activity. |
|
|
|
|
|
|
|

|

|
|
|
 |
|
|