| |
|
 |
|
 |
|
|
|

|
The CorrView
® corrosion monitor is a new product specifically designed
in response to the inherent inaccuracy of corrosion coupons, and to the need to
measure pipe wall loss under real world conditions. That is, under the same
conditions as exist for the pipe metal itself. CorrView ®
is also designed to provide long term and low cost wall loss monitoring where
conditions or interests do not allow for any form of regular corrosion testing,
and where no corrosion monitoring would be otherwise performed.
Unfortunately, corrosion coupons, the
most common form of corrosion monitoring used today, fall far short of
providing accurate corrosion rate data, and often produce wall loss estimates
dangerously lower than actually exist. Other testing methods, such as spool
pieces and LPR electronic monitoring, are often not practical on the scale
necessary to produce sufficient statistical information.

A history of
comparison between corrosion coupon results vs. actual pipe wall loss, as
confirmed by ultrasonic wall thickness testing, consistently shows an under
reporting of metal loss using corrosion coupons by 5 to 10 times - and in some
examples by as much as 200 times or more. For building operators or plant
engineers responsible for millions of dollars of mechanical equipment and
infrastructure, a total reliance upon questionable corrosion coupon results can
spell disaster - and often does. See Technical Bulletin
# C-14 for a case history of how a total reliance on corrosion coupons
concealed a major corrosion problem for
years.
This is not due to
failure of the metal coupon per se, which well represents the corrosion
potential of the liquid itself, but due to its placement externally to the
piping system. The coupon rack testing configuration inherently eliminates most
of the normal corrosion effects found within the pipe, and therefore less
effect is shown by the coupon under lab analysis. Corrosion coupons often
represent no relationship between the corrosion occurring at their surface, and
the corrosion occurring at the pipe surface.
Read more about the
limitations of corrosion
coupons.
Our own corrosion
studies have documented the similarity in wall loss between corrosion coupons
and common mild steel pipe samples under a controlled salt spray environment.
Side by side testing has shown a general similarity in corrosion rate when
under similar conditions - the key factor missing when coupons are installed in
an isolated side stream loop. View corrosion testing
reports
In effect, CorrView
® functions as the direct opposite of standard corrosion
coupon monitoring in two very important aspects. First, its wear surface is
located directly within the piping system, whereas the coupon wear surface is
located externally.
Second, time period of
exposure is decided in days or months for corrosion coupons, and the amount of
material lost through any corrosion activity is measured following that
exposure. With CorrView ®, the thickness of material to
corrode away is predetermined, and depending upon the existing corrosion
activity, the time that it takes to wear away will change. Fixed time vs.
varying metal loss for corrosion coupons, as opposed to fixed metal loss vs.
varying time for CorrView ®.

Adequately
monitoring a piping system for corrosion activity is generally prohibitive
using any of the previously available testing methods.
|

|
|
Installed in an isolated loop,
corrosion coupons never suffer the same environmental effects as the pipe
itself, and rarely provide accurate test results. Hardened deposits, electrical
activity, under deposit corrosion, micro biological buildup, flow effects, and
other common environmental factors typically do not exist for corrosion
coupons.
A flow requirement, by definition, prevents their installation
in precisely those locations traditionally showing the highest corrosion
threat.
In addition, installing corrosion coupon racks at multiple
points throughout a circulating system is not practical and is almost never
performed - thereby forcing the unlikely assumption that the test results shown
for one specific location are representative over the entire piping
system.

|
|

|
|
Periodically cutting out samples of
pipe for metallurgical analysis is extremely expensive, usually requires a
system shutdown, is rarely carried out for large diameter piping, and for any
critical or 24/7 operation - is virtually impossible to perform. Combined
maintenance and metallurgical costs can easily exceed $4,000 per
sample.
Metallurgical analysis does offer valuable information
unavailable through any other means, and is especially useful in order to
identify the cause of a corrosion condition, but is generally limited in use
due to its cost and inconvenience.
Metallurgical analysis usually plays
an inportant role in defining a corrosion problem, rather than discovering
one.

|
|

|
|
Spool pieces, which are nothing more
than removable sections of actual pipe within the system, provide valuable
information regarding the actual net effect of corrosion activity against the
pipe surface. Unfortunately they are only applicable for smaller diameter
piping separate from the main lines.
Properly installed, spool pieces
offer a true inside look at deposits, surface pitting, inhibitor and cleanout
effectiveness, as well as provide samples for micro biological cultures. Like
corrosion coupon racks, however, they are rarely installed throughout a piping
system and enjoy limited use.

|
|

|
|
Ultrasonic wall thickness testing
provides the greatest volume of reliable data, and will typically produce a
thorough corrosion evaluation as long as a sufficient number of test points are
taken.
Ultrasound is often used as a prerequisite to other testing
methods due to its low cost and wide coverage, or as a confirmation that wall
thickness conditions known to exist in one area do or do not exist elsewhere
within the piping system.
It is most often used as a tool to identify
the extent of an already recognized leak or rusting problem, and long term
corrosion monitoring using ultrasound requires establishing specialized testing
procedures. Read more about
ultrasonic pipe testing.

|
|

|
|
A wide variety of electronic
techniques eixst to produce an estimate of corrosion rate generally based upon
the principal of Linear Polarization Resistance, or LPR.
LPR provides
the benefit of an immediate corrosion measurement that can be routed to
monitoring electronices, or data logged for download, and offers an extremely
useful corrosion measurement tool.
LPR is generally expensive to install
and maintain. Regular celaning and calibration is often required, and even
then, results may not approximate true corrosion activity - expecially if
underdeposit corrosion or MIC is active.

|
|

|
|
The insertion of a remotely
controlled camera into the pipe offers a valuable thought very limited
inspection option. Its use requires the system to be out of service and
drained, and is greatly limited by access into the piping system. Pipe size,
physical configuration, internal conditions, and length of travel offer further
restrictions in its use.
Remote Video Inspection (RVI) cannot provide
any wall thickness data, but can quickly locate those internal indications that
wall loss has occurred - such as tubercular deposits, deep pitting, or
suspected MIC growths.
Combined with ultrasound or metallurgical
testing, RVI can quickly and cost effectively document whether similar problem
conditions exist in other areas of a piping system.

|
|

|
|
X-ray offers limited application for a
piping evaluation primarily due to its high cost and safety concerns. While
x-ray can provide the wall thickness values necessary for a true pipe condition
analysis, it is most often used for the inspection of weld integrity or for
identifying cracks, voids, or a major localized deterioration in a pipe
material.
Cost, health, and environmental issues severely restrict its
use in all but the most critical of applications.

|
|

|
|
Similar technology also exists for an
excellent but rarely used tool in measuring a wide variety of piping related
problems. Its use of safe, low powered gamma radiation rapidly identifies areas
of higher wall loss - quickly locating those areas in need of further
investigation.
By detecting variations in metal density, this hand held
device can also detect pipe blockages, identify wet insulation, show liquid
level, or confirm pipe schedules, etc. |

For many cooling
water loops, and especially for open recirculating systems, dramatically
different corrosion conditions can exist at various points throughout the
piping layout. Often, the actual causes of such corrosion differences, such as
at low flow areas or at long horizontal runs, are unavoidable. Similar
differences in corrosion activity can exist at different areas of a fire
protection system - for totally different
reasons.
Following 20 years of experience
in chemical water treatment and ultrasonic pipe testing, we have been able to
predict problem corrosion areas simply based upon the physical configuration of
the piping system. Some commonly recognized problem areas are summarized
below:
|

|
|
Lower floor areas of the same piping system typically suffer a
far greater degree of corrosion and pitting activity simply due to the settling
of dirt, iron oxide, organic material, and particulates.
Ultrasonic
testing results showing a 4 MPY corrosion rate at the upper floors of a
condenser water system, will often indicate substantially higher rates at the
bottom of the system. This higher wall loss in many cases also exists where
piping has been reduced in size and therefore in available wall thickness.
See Technical Bulletin
C-14 showing where a 6.5 MPY corrosion rate at the roof increased to a 22 MPY
rate at its lowest point.
A seemingly reasonable and moderate
corrosion rate of 5 MPY will actually produce tremendous volumes of iron oxide
each year which will settle to produce secondary problems if not removed.
See Technical Bulletin
# C-1 for the actual pounds of metal lost and deposits created at various
corrosion rates.

|
|

|
|
Horizontal sections of pipe typically show a higher degree of
sediment and deposit buildup, corrosion, and pitting than vertical sections -
for the obvious reason.
Coupled with low flow conditions or the periodic
loss of flow, as might occur with individual HVAC package units, horizontal
piping can suffer at significantly higher corrosion rates.

|
|

|
|
Within horizontal sections of pipe,
and often depending upon flow rate, the bottom and lower side wall areas often
show significantly higher metal loss - again due to the settlement of rust and
particulates.
Even under 24 hour moderate flow conditions within large
diameter main riser piping, ultrasonic testing has often documented the
presence of under deposit activity - as suggested by a randomly elevated
corrosion rate and in some cases deep pitting.
The presence of
significant differences in wall thickness from top to bottom of any same
section of horizontal pipe should always provide a warning of an interior
deposit problem.

|
|

|
|
The net result from various corrosion
mechanisms is often deep and random pitting which can only be defined through
metallurgical analysis.
The presence of a micro biological agent or MIC
condition is especially effective at producing random areas of extremely high
wall loss often exceeding 25 mils per year (MPY). This produces often
devastating results and is extremely difficuly and costly to correct. See Technical Bulletin
C-5 regarding the MIC threat.

|
|

|
|
Piping which is drained down over the
winter months, or which is shut down and drained periodically, can suffer up to
10 times greater wall loss than other filled areas of the system. Such
corrosion loss is often directly proportional to the proximity to the open
atmosphere.
This is a common problem for many northern properties
regardless of the standard lay-up precautions taken.
See Technical Bulletin
C-3 about this well documented problem.

|
|

|
|
Return side piping at a condenser or
cooling water system often shows a higher degree of corrosion and pitting than
for the supply side - this may be due to the slightly higher return water
temperatures which favor corrosion activity and promote micro biological
growth.
Higher return side corrosion may also be due to the secondary
effect of rust particulates originating from the supply side pipe, or other
factors.

|
|

|
|
Due to the generally lower quality of
steel pipe today in comparison to that manufactured 50 years ago, higher
average corrosion rates are common. Where 1 MPY corrosion rates once existed
many decades ago, 3-5 MPY corrosion rates are now expected. Pipe produced
outside the U.S. seems especially more corrosion susceptible.
For
reasons not fully understood, new piping additions and renovations will often
show a higher corrosion rate than for the original piping itself. Any new pipe
should therefore always be monitored equally or even more closely than older
areas of the system.

|
|

|
|
Stagnant areas can often develop
severe pitting from the settlement of particulates and/or a lack of chemical
protection. The lower flow rates existing in the distribution and run-out
piping to individual A/C or package units will often show accelerated corrosion
in those smaller lines which can least afford it.
Dead ends, by-pass
lines, futures, lead and lag equipment, mud legs, and other no flow areas can
produce corrosion rates well exceeding 15 mils per year, and accelerate pipe
replacement decades before the rest of the system.

|
|

|
|
Rarely a corrosion related factor in
the early stages of a piping system, pipe construction does play a critical
role in an aged system. End gaps of a Victaulic, Grinnell or other clamped type
piping system often accumulate with particulates and micro biological agents to
produce localized high corrosion and pitting losses.
Threaded pipe will
almost always leak or fail prior to other areas due to the 50% or greater wall
loss produced in the threading process, among other factors.
See Technical Bulletin
P-1 regarding the inherent weakness of threaded pipe.
Cutting
the groove into pipe used in clamped pipe assembly, rather than rolling or
swaging it, has the similar effect of significantly reducing pipe wall life.
This wall loss, coupled with a high corrosion rate, will typically produce
advanced failures. See Technical Bulletin
P-3 about the threat created by cutting the groove for clamped pipe
construction. |
Obviously, pipe
corrosion activity is a complex mechanism which cannot be reliably predicted by
any one means. It is therefore necessary to establish a corrosion monitoring
program that will not only provide accurate and relative information to what is
actually taking place at the pipe, but to also address those areas of the
system where elevated corrosion activity is likely to take place.

It is important
to remember that while the variance in wall loss, corrosion rate, and pitting
will fall within a certain range of values for most piping systems, that range
of values will widen substantially when a serious corrosion problem exists. As
corrosion rates and pitting activity increase, so does the probability that
random piping areas may produce sufficient weakness in the pipe to cause a leak
or operating problem.
This greater
fluctuation in corrosion rate simply increases the existing danger of having a
corrosion rate determination based upon only one monitoring technique, and at
only one monitoring location.
It was with
the interest to address such concerns that the CorrView ®
corrosion monitor was invented. CorrView ® has been
awarded Honorable
Mention in the 2004 AHR Expo Innovation Award Competition.

©
Copyright |
|
|
|
|
|
|

|

|
|
|
 |
|
|