| |
|
 |
|
 |
|
|
|

|


The interior of
any HVAC piping system can show a wide range of corrosion characteristics -
those characteristics and their severity being dependant primarily upon piping
service, followed by physical orientation, age, pipe size, and
location.
Corrosion problems do not appear
overnight, and are generally the result of a failure to provide good chemical
inhibitor protection over an extended period of time. While other factors, and
the failure to take certain preventative measures may also apply, high
corrosion rates are very often related to the volume of rust deposits which
have accumulated. The volume of such deposits, and their ultimate affect, are
in turn, generally dependent upon the type of water service involved. While
there are always exceptions, the follow generalizations apply:

|

|
|
Steam piping wears uniformly along its interior surface, and at
low corrosion rates typically near 1 MPY or less. Lower rates are generally
found where the steam is produced from an on-site boiler having a good chemical
treatment program, as opposed to a city source or private utility.
Steam condensate systems wear at higher and less uniform corrosion
rates, at horizontal sections rather than vertical ones (more so at the bottom
of the pipe), and can suffer extreme pitting due to the generally acidic nature
of steam condensate. Chemical treatments to control condensate corrosion, while
available, are rarely provided.

|
|

|
|
Closed hot water, cold water, and secondary systems, unless
neglected or periodically opened to the atmosphere for free cooling service,
typically show low to moderate corrosion rates of under 1-2 MPY. Only under
unusual conditions, such as where a severe microbiological problem exists, will
a secondary system produce a threatening corrosion condition.
It is
especially important to note that closed chill water and secondary systems,
when directly cross connected to the condenser water system through a
Strainercycle or other full flow filter, will exhibit much higher corrosion and
pitting levels, and should therefore be viewed and treated as an open water
system.
For closed circulating systems, adding a side stream basket
filter is perhaps the most effective and low cost solution to removing any iron
oxide deposits which are naturally produced.
See Technical Bulletin
# W-1 regarding the use of side stream filtration to maintain clean closed
systems.
In addition, chemically cleaning and sterilizing all
closed systems every four years is highly recommended.

|
|

|
|
By far, open condenser water or
process water piping suffers the most widespread and severe corrosion related
problems of any HVAC or process plant recirculating system. This occurs even
though the majority of any chemical water treatment budget is typically devoted
to this area of operations.
While some properties may enjoy relatively
trouble free operation with a minimum of maintenance, others will see
significant deterioration and wall loss after only a few years.
In many
years of performing ultrasonic pipe testing, CVI has documented condenser water
piping with widely varying conditions - some having a wall loss of only 45 mils
over 60 years of operation, and others showing that same amount of loss within
2 years. Review a summary of
piping quality, operating, and design changes which have
occurred.
The many different corrosion types often existing
at a cooling tower system mandates close monitoring of such systems, as well as
the need to take certain precautionary measures to prevent their
development.

|
|

|
|
Fire sprinkler piping will corrode
greatly dependant upon the flow of water through the pipe. Where the system is
filled and left to stand undisturbed, a small amount of corrosion takes place,
oxygen is depleted, and the corrosion activity virtually ceases. Therefore, it
is not uncommon for measure a 25 mil loss of steel from stagnant fire standpipe
systems after 70 years of service.
Where the sprinkler system is
frequently drained for renovation or some other purpose, and especially where a
slow leak exists, corrosion will rise dramatically, but still provide generally
long service.
Dry or preaction systems offer a separate problem in that
after testing, the water can never be fully drained, and therefore, with an
abundance of oxygen, begins an attack along the bottom of the pipe.
The
more recent use of schedule 10 pipe has added significant threat to fire
service piping since the extremely thin wall piping, half of schedule 40,
leaves little room for corrosion to occur before reaching minimum standards and
failure.

|
|

|
|
Domestic water systems deteriorate
primary based upon a combination of age and the material of construction. The
common use of galvanized pipe for such services provides a service life
dependant upon the water chemistry of the geographical area, its quality, and
age.
Typically, once the galvanized coating is worn away, all the
electrochemical forces in the area focus on that unprotected section of pipe -
producing aggressive and random pitting. Properties in New York city typically
show such effects after 75 years, while properties in Chicago have been
documented to show no noticeable wear within the same period of
time.
Brass piping generally shows a low and even rate of corrosion
wear, but will eventually suffer from dezincification depending upon age and
the aggressiveness of the local water supply. Though more expensive, copper is
the choice of installation material today. |

High corrosion
rates, those which would be termed threatening to the piping system, depend
upon a combination of many different and possibly unknown chemical/electrical
mechanisms. Very often, they are related to the accumulation of iron oxide
deposits, often termed "tubercles," at the pipe surface. In short, an
ultrasonic finding of a high wall loss exceeding 10 mils per year (MPY) means
the existence of interior pipe wall deposits. Conversely, visually observing
large interior deposits and tubercles guarantees metal loss at the pipe. One
cannot exist without the other.
Interior
pipe deposits are always the result of some form of corrosion activity,
combined with captured particulates and organic or microbiological material. As
that corrosion activity continues over time and heavier deposits are allowed to
accumulate, chemical activity beneath such deposits may develop into different
forms commonly known and generally termed as "under deposit" corrosion.
Such deposits represent a far worse threat to the pipe than just a loss of heat
transfer or flow.
In its least damaging
form, under deposit corrosion may produce mild surface indentations over a wide
area, yet leave the pipe in still serviceable condition. But in its more severe
form, under deposit corrosion will produce narrow and deep pitting - which may
in turn may result in advanced pipe failure within 10 years or less.
Ironically, the higher the corrosion
rate, the more deposits produced - and the more deposits produced, the higher
the corrosion and pitting rate. It is a difficult to stop downward spiral,
requiring substantial effort and cost to stop.

The below side by
side comparison shows a section of domestic water galvanized steel pipe
uniformly covered with a 1/4 in. to 1/2 in. layer of iron oxide deposits.
Removing the deposits using a high pressure water jet revealed widespread
though shallow depressions into the pipe wall, and no significant threat to the
remaining service life of the pipe. Ultrasonic thickness testing proved the
pipe suitable for further service.

The more serious
scenarios of "concentration cell" and "oxidation cell" type
corrosion often define themselves as having a much heavier buildup of corrosion
product at isolated areas, and little to no corrosion product elsewhere.
Instead of attacking the entire pipe surface, such corrosion types focus all of
their activity at specific points. In such cases, it is common to measure some
existing wall thickness values at or near new pipe specifications, and then
locate areas of high deterioration having perhaps a 75% or greater wall loss.
This is especially common at galvanized
pipe.
Shown by the below right photograph
after physically removing the iron oxide deposits at the left, deep 0.125 in.
depressions exist at this 12 in. ASME A 53 steel condenser water pipe. Yet the
surrounding areas show virtually no wall loss whatsoever. It is this high
degree of localized corrosion activity, resembling the action of a drill bit,
which will dramatically shorten the service life of any affected piping system.


Whether
eventually creating shallow and generalized wall loss, or deep and localized
pitting, the buildup of iron oxide deposits always represents a serious threat
to any piping system. Therefore, a high importance should always be placed upon
removing such deposits in order to stop or minimize any underlying corrosion
activity. Preventing the establishment of such deposits is obviously a
preferred maintenance or operating strategy, and can be generally achieved
using a combination of good water treatment, supplemental filtration, and
chemical dispersant. See Technical Bulletin
# C-2 for recommendations on maintaining good corrosion
control.
Our experience, both
in ultrasonically testing pipe at hundreds of building properties, and by
inspecting metallurgical samples, has shown a very clear relationship between
the extent and profile of the interior deposits, and the wall loss damage
incurred. In all examples, heavier deposits will define a more severe pipe
loss.
The danger of deep pitting caused by
heavy rust deposits or tubercles is further illustrated in the below
photographs. Here we show generally even and acceptable remaining wall
thickness throughout most of the pipe wall, but with severe and localized
pitting hidden under those areas where the heaviest interior deposits exist.
This is shown at the left side of each photograph. Settlement of particulates
at the bottom of the pipe proved to be the cause of this problem - resulting in
the total penetration of random sections of both 12 in. schedule 40 condenser
water pipes within 10 years.


Accumulated
deposits may also create conditions favorable to extremely destructive
microbiologically influenced corrosion, or MIC - the general term for a wide
group of microorganisms which often produces their own acidic environment, and
have been documented to virtually dissolve steel pipe at corrosion rates
exceeding 50 MPY.
Interior deposits
provide attachment points, nutrients, insulation from microbiocides, and other
benefits all encouraging the growth and spread of this most serious form of
corrosion attack. See Technical Bulletin
# C-5 for further information on MIC corrosion.

Typically not
indicated through corrosion coupon monitoring, the most common form of
corrosion testing employed, under deposit corrosion is often identified after
its presence is noticed through other means. Overall, the damaging effects of
under deposit corrosion include:
- High corrosion rates exceeding 25
MPY
- Produces conditions favoring MIC
- Higher maintenance costs
- Higher operating costs
- Premature piping failure
- Obstruction at cooling tower drip
pans
- Fouled cooling tower basins
- Clogged condenser tubes
- Overloads many non-automatic filtration
systems
- Prevents chemicals from reaching the base pipe
metal
- Reduces heat transfer efficiency
- Clogged heating and cooling coils
- Promotes galvanic corrosion near brass or
copper
- May cause abrasive wear in high velocity
areas
- Premature refrigeration equipment
failure
- Restricted water flow
- Unpredictable shutdown of equipment on high
head
- Damages expensive mechanical pump
seals
- Damage to heat sensitive equipment
- May prevent isolation valves from
operating
- May prevent actuators and control valves from
operating
- May produce false sensor readings

Under deposit
corrosion activity can be generally identified without the need to remove
samples of pipe through the use of ultrasonic testing. Due to the very random
nature of such pitting, a significant amount of testing is often required to
ensure that such conditions are identified, if they exist. A metallurgical
examination of a removed sample of pipe is also recommended to confirm any
suspicion, and a laboratory culture or DNA analysis of the under deposit
growths is recommended in order to determine if MIC is
present.
The best solution, of course, is
to prevent such deposits from developing in the first place. This, however, is
easier said than done. In many cases, such problems reveal themselves only
after producing a water flow loss, heat transfer problem, obvious rust sediment
in the strainers or pans, or a leak condition. Buckets of rust and scale
following spring start-up or after a shock to the system are clear indicators
of a problem. In some examples, a service repair or renovation may allow entry
into the piping, thereby revealing the extent of the problem for the first
time. Frequently, such problems are inherited from previous building owners,
operating personnel, or an HVAC
contractor.
As discussed previously,
strict reliance on standard corrosion coupons often allows many years for under
deposit corrosion to develop and worsen, while at the same time providing metal
loss results only applicable to the corrosion coupon itself. In many cases, we
have been advised of corrosion coupon rates well below 1 MPY, and yet, through
extensive ultrasonic testing, have found interior corrosion conditions similar
to the above examples with actual corrosion rates exceeding 10 MPY. It is a
very common scenario. Read more about the
many limitations of corrosion coupons.
Corrosion coupons will show whether a
water treatment chemical exists, and whether or not it is effective to control
the corrosive attack against a new coupon sample. Rarely, however, does it
reflect actual corrosion at the pipe surface, and in fact, we highly discourage
relying exclusively upon corrosion coupons as a measurement of corrosion
control. The CorrView ® monitor has been designed
specifically with such limitations in mind, and is intended to provide a more
realistic corrosion rate assessment. Read more about the
many advantages of CorrView ®.

Obvious
recommendations to prevent such problems include a strict and automated
chemical water treatment program, good water filtration, better corrosion
monitoring, and added dispersants or cleaners to control those deposits which
will inevitably result. While there is no absolute guarantee for trouble free
condenser water operation, the below recommendations will significantly reduce
the possibility of being surprised by a severe pitting condition.
- Do not rely on
corrosion coupons to indicate corrosion activity
- Maintain a
strict water treatment program
- Monitor the
chemical treatment program closely
- Automate all
chemical feeds and bleed-off
- Install a 3 in.
to 6 in. inspection spool piece in at least two locations
- Perform a
visual inspection of the pipe whenever possible
- Verify that
water flow rates are adequate to prevent settlement
- Eliminate any
low flow areas
- Use borescope
or robotic camera to inspect the pipe interior
- Provide flow
by-pass through any A/C units when off
- Perform
ultrasonic testing to establish actual corrosion rates
- Add full flow
or side stream water filtration
- Avoid draining
down the piping
- Properly
lay-up the pipe when drained down
- Consider the
services of an outside chemical consultant
- Chemically
clean the condenser or open water piping twice per season
- Chemically
sterilize the condenser or any process water piping twice per
season
- Add a
dispersing agent to the regular chemical program
- And of course,
add CorrView ® monitors at specific areas within the
piping system.

Some additional
photographs of the above interior deposit problem are presented in a short
photo gallery from actual CVI case histories.
View our photo gallery
of interior pipe deposits.
In
many examples, a combination of conditions will exist within the same piping
system - therefore requiring sufficient monitoring over enough locations to
provide a reliable corrosion rate assessment.
View a photo gallery
of common piping failures. In virtually ever case we have been
involved, better precautionary measures, combined with more thorough and
accurate corrosion monitoring and faster and more effective corrective actions,
would have prevented such problems from occurring.
©
Copyright
|
|

|
|
|
|
|

|
|
|
 |
|
|