Steel cold
domestic water storage tanks, often called house tanks, are generally viewed as
low maintenance, long service life structures necessary to most larger building
properties and some process plants. The taller or larger the property, the more
tanks which may exist, and larger in size. In addition to providing a cold
water supply at the appropriate pressures, they often also provide reserve
water for fire protection, and range in size from 2,000 gallons to 60,000
gallons and greater.
Those used for
potable water storage, by law and local codes, must be regularly cleaned and
sterilized on the inside by licensed professionals in order to satisfy health
concerns. Tanks situated in moderate to high traffic areas typically receive a
coat of paint on the exterior of their exposed and accessible surfaces and are
well maintained. Those tanks which are hidden away in basements, roof areas,
and corner storage rooms, not surprisingly, are often
ignored.
On the inside, corrosion
protection is achieved strictly by placing a boundary or isolating coating
between the water and the steel plate. Annual inspection and cleaning, if
performed properly, generally raises notice of any coating deficiency, and
provides the opportunity to make repairs before significant damage occurs.

A common area of
interior wall loss occurs at the area of the water line. Here, constant washing
back and forth over the same area tends to fail many protective coatings, and
then heavily damages the underlying steel. The below sample graphs, created
after performing 400 to 500 or more ultrasonic measurements per side wall, well
illustrate not only this particular problem, but the power of ultrasound to
produce a virtual 3-D dimensional profile of each interior tank wall and
bottom.
At the left, ultrasonic testing
along a standard X-Y grid at the side tank walls produces a clear picture
showing a failure of the coating and the resulting corrosion at the water line.
We see the uniform wall thickness profile below the water line, to the right,
and the slightly more corroded area above the water line to the left.
At the right side graph, based upon a
separate ultrasonic investigation, we can show an extremely uniform wall
thickness at the front and back sides. No corrosion exists at the exterior, and
the inside coating is obviously intact - as average wall thickness exists
virtually at the specification for this steel tank.
|

|

|

The same
maintenance level is rarely assigned to the outer tank surface, however, which
often results in metal deterioration ranging from mild to severe. Worst of all,
the most severe tank damage is generally hidden from view, and can
significantly worsen over decades given certain
conditions.
Exterior steel tank
deterioration is due to a variety of physical factors - water temperature, tank
temperature, tank size and location, construction, area humidity, coating
effectiveness, tank supports, and physical accessibility. While interior
coatings do provide generally good corrosion protection, their periodic failure
often results in localized areas of wall loss. Exterior wall loss, however, can
equal and often exceed that occurring on the
inside.
For larger tanks, the cold inlet
water will often settle to the bottom rather than mix to produce a uniformly
moderate tank temperature - therefore it is quite common to find a significant
temperature gradient between top and bottom. Given sufficient humidity, such as
is typically found in a mechanical room area, surface condensation can develop
to the point of producing a moisture boundary layer, and even water droplets,
at the tank's bottom and lower
sides.
Condensation, and the resulting
corrosion it produces, is not only far more prevalent at the bottom of the tank
due to the colder surface temperatures, but produces the greatest damage in
that area simply due to the fact that it is out of normal view. It is almost
unheard of to find the underside of any steel tank, and its supports painted or
in any way protected - thereby allowing corrosion free travel if conditions
permit.
Condensation collected onto outer
tank walls can similarly produce a corrosion problem, but to a lesser degree if
it is noticed and corrected by building maintenance personnel. Most side wall
corrosion problems exist where tanks are placed directly against one or more
walls. In many cases, tanks are constructed only a few inches away from two or
more walls, often because they are built in place, and thereby prevent any
maintenance or inspection from being performed.

Given sufficient
time, and a protective coating which is not uniform, not well adhered to the
metal, or having damaged areas or entry points, moisture will eventually
deteriorate most steel tank walls. In most examples, standard industrial paints
are used where specialty coatings are actually
required.
With an entry point established,
moisture will condense beneath the protective coating and gradually work its
way under the coating to produce a blistering of the tank surface. In some
cases, as much as a cup of water has been found trapped underneath a single
coating blister, and against the bare steel surface. This corrosion mechanism,
however, is a very long term process - typically requiring decades to fail a
steel tank.
Exterior corrosion is
especially common at older riveted steel tanks having irregular surfaces where
the paint or coating may not be of uniform thickness. In many cases, blistering
can extend over wide areas, producing a deeply pitted surface due to direct
contact with what is essentially untreated
water.
Often, the greatest damage caused
to the bottom of a house tank is not at the tank surface, but at the tank to I
beam supports. Here, a combination of moisture, no corrosion protection, and
mild galvanic activity between tank and beam, can actually undermine the tank
bottom. A variety of common problems found at house tanks is provided in the
below photo gallery.

|
 |
|
 |
Moisture Condensation - This view
of a tank bottom shows the entire surface covered with water droplets.
Excess moisture over many decades has completely worn away sections of
the original I beam support under the tank. |
|
Tank Failure -
Isolated pitting failure at the interior of this tank prompted repairs by
welding patches of steel over the affected area.
Unfortunately, the
recently installed patches were not sealed with any protective coating -
thereby rusting themselves. |

|
 |
|
 |
Riveted Seams - Commonly found at
very old tanks installed before the 1950's, riveted seams can be a frequent
source of problem.
Due to the low pressures involved, only one set of
rivets typically attaches overlapping steel plates - thereby providing less
sealing strength and greater chance for corrosion to occur and a leak to
begin. |
|
Cold Water Settling - Cold water
generally settles to the bottom area of any large house tank to produce this
result. Insulation is almost never provided.
Where the steel is lacking
adequate corrosion protection, some degree of corrosion and pitting usually
results. Metal loss at the bottom of the tank is usually the most severe.
|

|
 |
|
 |
Rust Accumulation - Years and
decades of moisture condensing at the bottom of a tank and producing water
droplets of iron oxide often produces a deep layer of rust at the bottom pan.
This rust is, in effect, the old steel from the tank bottom, and
indicates the degree to which a problem exists. |
|
Lost Tank Support - Corrosion
activity between the tank bottom and I beam support is a common problem.
Accumulated rust product, because it is less dense than its original
steel, can actually raise a tank from the I beam, or when lost, can create
large gaps having inadequate tank support. |

|
 |
|
 |
Bottom Moisture - Water and
moisture can easily accumulate at the tank bottom or holding pan easily under
high humidity conditions.
The above photo clearly highlights the
deterioration of the I beam support caused by such moisture. |
|
Exterior Coating Failure - A
common occurrence, especially where cold temperatures and high humidity exists
in the absence of acceptable maintenance.
Any small failure of the
coating usually extends to other areas to produce a greater problem. |

|
 |
|
 |
Maintenance Neglect - This
domestic water house tank shows clear evidence that it is in need of
sandblasting and the application of a good quality protective coating.
Patchwork repair is not likely to provide acceptable corrosion
protection since other problems areas will develop. |
|
Bottom Corrosion - This represents
a most difficult problem area since substantial corrosion product often
accumulates between the tank bottom and tank support base.
A
penetrating chemical rust inhibitor would be suggested. |

|
 |
|
 |
Bottom Loss - This domestic water
house tank shows a very common problem at the bottom I beam support.
A
combination of exterior moisture, galvanic action, and lack of paint has
created a large wall loss and gap between tank and supports - part attributable
to wall los and part due to raising of the tank from the rust expansion.
|
|
Support Corrosion - A regular
accumulation of exterior condensate at the bottom tank trough produced a severe
deterioration of the outside I beam supports.
Any water collected near
metal should be quickly removed in order to prevent accelerated corrosion.
|

|
 |
|
 |
Coating Failure - This side wall
of a domestic water house tank showed multiple examples of blistering to reveal
moderate to deep pitting. Such exterior corrosion is often at the lower area of
the tank where colder water has settled.
Scraping away the blisters
released water which had penetrated through the painted surface to condense
against the steel to produce a localized corrosion problem. |
|
Corrosion at Fixtures- Corrosion
activity at a threaded fixture always presents a greater threat due to the
inherently lesser thickness which exists at the threads.
Aside from the
generally lower wall thickness of a threadolet or other welded fixture, the
connecting pipe will have lost wall thickness due to interior corrosion,
threading, and external corrosion combined. |

A preliminary
inspection for exterior water tank corrosion can be usually performed in-house
by carefully looking over the entire structure, top to bottom, and at every
side. Special attention, of course, should be provided to the bottom of the
tank, at I beam supports, and at any areas which are generally out of
view.
A higher level of tank inspection
involves more than just a visual examination for surface rust, and typically
utilizes ultrasonic testing to identify remaining tank thickness and ideally -
a tank wall thickness profile. An analysis based upon the results of an
ultrasound test will generally follow API inspection specification 650, and
take into account other physical factors such as:
- Tank shape and
size
- Tank supports
and spacing
- Tank
construction - riveted or welded
- External
corrosion
- Tank to support
corrosion
- Wall thickness
profile
- Minimum
acceptable wall thickness limit
- Corrosion rate
- Construction
joint efficiency
- Corrosion
trends
- Remaining
service life
- Percentage of
allowable loss
- Overall
condition or status

The repair of
such external corrosion problems generally depends upon the physical location
of the corrosion activity. In accessible areas such as side walls, it is only
necessary to thoroughly scrape away the corrosion deposit and old coating, and
re-coat the surface.
Where damage has
already occurred and the surface is heavily pitted, we recommend sand blasting
prior to applying any coating, as only sand blasting can be assured of
producing a reliable metal to coating bond. In humid environments, specialized
coatings suitable for marine use would be recommended instead of common
industrial paints.
Tank bottoms always
demand the most difficult repair - especially where corrosion exists at the
tank to I beam supports. Here, the corrosion product may be to difficult to
remove, metal damage may be too advanced to simply paint over, and major
reconstruction may be necessary in order to replace the tank support lost due
to corrosion.
Adding I beam supports
maybe necessary due either to the loss of bottom wall thickness, or due to a
weakness of the supports themselves. Completely inaccessible areas may require
other repair alternatives, such as penetrating coatings or isolation and
dehumidification of the entire house tank area in order to hopefully slow the
corrosion process. Lay-up chemicals that will effectively penetrate rust
deposits and protect the underlying metal surfaces exist, and offer an
excellent option in some applications.

While common to
domestic water steel holding tanks, high exterior wall loss is possible for any
vessel which operates at very low temperatures in the presence of humidity.
Such may exist at brine and ammonia refrigeration systems even though they are
typically protected from moisture condensation through the use of heavy
insulation. A periodic visual inspection is therefore always
advised.
Any breaks in the insulation will
provide an entry point and high localized wall loss. This is especially true at
any threaded fixtures which are inherently difficult to properly insulate.
Small diameter pipe also provides a lower wall thickness, is reduced 50% or
more due to threading losses - placing any inlet and out piping often at
greater risk. The application of a high quality protective coating is well
recommended.
While there are many examples
where corrosion cannot be controlled, the deterioration of any cold water tank
due to lack of maintenance is generally avoidable.
©