Line


     Over 20 years of experience in chemical water treatment and ultrasonic pipe testing has provided CorrView International an excellent understanding of many common corrosion related problems found at commercial office properties and plant facilities. Indeed, we see the same corrosion problems again and again - which indicates to us some clear and unmistakable trends for different piping systems and operating conditions.

     We offer below some general guidelines of where corrosion problems might exist and why. Many corrosion scenarios are linked to others obviously in similar cause or effect. Although the corrosion issue is complex, and may present itself in many different forms, it often begins due to some simple initiating factor - a lack of chemical treatment, or a faulty start-up of the system, for example. The presence of a corrosion problem in any particular area should always raise concern and the need for further investigation.


Higher corrosion rates are often found at the return lines for open process or cooling tower systems. This difference does not commonly exist in closed systems.

Sorting a large set of testing data based upon flow direction for a condenser water loop will often show this difference quite clearly - with 1-3 MPY higher return side corrosion rates not uncommon.

One suggested cause is that the higher temperatures returning to the cooling tower naturally accelerates the corrosion activity, and/or that it provides a more suitable thermal environment for microbiological growth.

Another is that the iron oxide created at the supply side piping then has opportunity to migrate downstream to the return side - where it is more likely to deposit and create higher corrosion conditions. See Technical Bulletin C-4 about the problems associated with interior deposits.



This is an obvious problem well recognized by most experienced plant engineers and property owners - and which becomes most pronounced as either the length of the horizontal or vertical pipe run increases.

Particulates, and especially those heavier components, settle out in the horizontal lines based upon the length of pipe, flow velocity, and pipe diameter. We consider interior deposits to be one of the most serious problems affecting any piping system due to the secondary damage usually created.

This problem exists for open and closed systems both, but more so obviously at open cooling systems due to the greater source of airborne particulates, microbiological content, and due to the naturally higher corrosion rates of an open system. See Table C-1 for the actual pounds of metal lost at various corrosion rates.

For tall commercial building properties, the vertical risers often show substantially less corrosion and pitting than the horizontal runs. Longer vertical runs increase the difficulty for particulates to migrate upward and therefore horizontal settlement increases. Larger volumes of pipe also produce a greater volume of iron oxide deposit which inevitably settles elsewhere.

For large process and manufacturing plants spanning acres of floor space, particulates entering any length of pipe may not remain suspended, but instead settle throughout the distribution lines. This problem is amplified as the piping branches off into smallest lines, and as the distance from the circulating pumps increases - thereby lowering flow velocity.



Three separate corrosion scenarios can exist to produce a noticeable difference between pipe located at the top and bottom of the same system.

The first involves the settlement of particulates into the lowest points of the system to produce an under deposit condition with substantially higher corrosion rates.

Second involves the layout of the piping system, and whether significant enough differences in flow rate exist to influence the effectiveness of the chemical treatment program and/or cause the deposition of particulates.

Depending upon whether the system is partially drained over the cold weather months, a third possibility may be the substantially higher corrosion which occurs at any pipe which is drained and left open to the atmosphere. This is a common problem at roof level piping. See Technical Bulletin # C-3 about increased corrosion activity during winter or temporary drain down.



Drained pipe is usually linked to the most serious corrosion losses. In many cases, a high corrosion condition will be traced back to years earlier - when some event required the temporary or extended draining of some or all of the pipe. In comparison, drained piping produces significantly greater metal loss than pipe filled with fresh and untreated water.

The degree to which draining causes damage is directly related to the infiltration of fresh air into the pipe. Therefore, it is common to find a high wall loss at the cooling tower side, and a sudden increase in wall thickness after an isolating valve, or as the pipe travels further toward a dead end. See Technical Bulletin # C-3 about increased corrosion activity during drain down.

Any effort to maintain a piping system filled with chemically treated water is highly recommended. This includes insulating and heat tracing outdoor lines in colder climates, and installing critical isolating valves. Another option is to use extremely effective VCI chemical inhibitors where possible. See Technical Bulletin # C-9 for further information on VCI corrosion inhibitors.



  For a wide variety of reasons, threaded pipe almost always shows the first sign of a corrosion problem. This is primarily because as much as 65% of the available pipe wall is cut away during the threading process itself on day one. See our thread loss table. This small diameter pipe also offers inherently less wall thickness - thereby an already thin material is reduced even further.

Threaded pipe usually exists at lower flow areas, and at the furthermost extremes of the system at the process equipment or A/C units. Here, flow rates are the lowest, or may be periodically shut down altogether - two additional factors commonly associated with higher corrosion rates.

Threaded pipe almost always involves brass valves or a transition to copper pipe. This often creates a galvanic corrosion condition at the threads since, in the majority of examples, dielectric insulators are absent.

Gaps at the pipe fittings also offer opportunity for particulates and microbiological growths to collect and produce a localized corrosion problem - once again focused at the very weakest point of the system. While adequate pipe may exist along 99% of its length, a failure at the threads usually means the end of service for the entire pipe length.



Any piping investigation, if thorough, is likely to identify some higher degree of corrosion at the horizontal and/or lower floor piping. This is obviously due to the settlement of particulates in this area, and the secondary corrosion effects such particulates create.

In many of those cases, a substantial increase in corrosion activity and wall loss can be measured at the bottom and lower sides of the horizontal runs. Primarily dependent upon flow velocity, particulates settle, and tubercles of iron oxide develop to produce extremely high under deposit corrosion rates of 25 MPY or greater. View a good example of this problem.



No flow areas of piping can demonstrate dramatically different corrosion scenarios. Where isolated and truly stagnant, such as exists for a fire standpipe system, a small amount of corrosion takes place and then further corrosion activity virtually ceases. It's not unusual, therefore, to measure remaining wall thickness values near new pipe specifications in such cases.

Where new water is introduced in to a dead end, by-pass, or isolated pipe section, results can be the opposite, and extremely high corrosion activity often becomes established. By definition, such areas of pipe are never tested for corrosion - as no flow exists to route water to and from a corrosion coupon.

Any by-pass loops, especially those having the downstream side closed by a valve, are high priority areas for severe pitting corrosion to develop. This occurs when particulates enter and settle out in the pipe in high quantities to produce severe under deposit pitting, and is quite common.

Pipe serving lead and lag equipment, or where the water flow is shut down when the equipment is de-energized, is especially vulnerable to much higher corrosion activity.



Higher corrosion rates are often found at the new pipe following a pipe repair, replacement, or extension to an existing system. This is especially common at condenser or open process water systems.

One easy explanation is the better quality and higher corrosion resistance of pipe produced decades ago. Its not unusual to measure a 1-2 MPY corrosion rate at 40 year old pipe, and a 4-5 MPY corrosion rate at newly installed pipe within the same recirculating system.Review a summary of piping quality, operating, and design changes which have occurred.

In many examples, iron oxide and other particulates quickly migrate into the new pipe to produce an accelerated under deposit condition. Where new pipe is installed downstream of older constricted pipe, the greater volume of the new pipe slightly drops the velocity and therefore allows more settling of particulates.

Galvanic activity between new and clean pipe and old and deposit laden pipe is also recognized as occurring - although the mechanism is not completely understood.


     In many cases, identifying a corrosion problem is simply a question of looking in the right direction. Quite often, no problem is known about, nor even suspected, until some special interest is raised. Under the worst case scenario, a problem may exist for years and exhibit no indication to the property owner, operators, or chemical treatment contractor.

     Ultrasonic testing excels as the most valuable corrosion monitoring tool for the purpose of finding hidden faults since it provides a quick and low cost method of determining wall thickness. Coupled with a thorough data analysis, ultrasound can provide an almost complete understanding of piping system integrity. Areas of concern raised can them be confirmed or further investigated through metallurgical testing or other methods.

     As long as sufficient testing is performed by skilled and experienced personnel, and as long as key problem areas as outlined above are addressed, ultrasound will produce a thorough and reliable system evaluation. See Technical Bulletin P-7 for more about the level of information provided by ultrasonic testing.


Review our disclaimer on any technical information contained within this Internet site.


©  Copyright






Line