| |
|
 |
|
 |
|
|
|

|


The most critical
piping system for any building property or plant operation is unquestionably
the fire sprinkler service. Often considered trouble free, corrosion related
failures at fire sprinkler lines have dramatically increased over the past
decade - raising not only operating and repair costs, but the threat to
building inhabitants as well.
By
definition, fire sprinkler service always exists under a corrosion threat since
carbon steel black pipe is traditionally used, and its water is never
chemically treated. This raises the importance of recognizing and addressing
other corrosion influencing factors in order to maximize its useful service
life.
CorrView International's 10 year
involvement in ultrasonically testing fire sprinkler systems has provided us
with an extensive database of hard, factual wall loss and corrosion rate data.
It has also allowed us to identify very clear relationships between the design
and operation of fire sprinkler systems, and resulting corrosion conditions.
Prior investigations have identified 75
year old sprinkler pipe in virtually new condition, and yet nearly new 4-5 year
old installations in need of replacement. Clearly evident, a much higher
incidence of corrosion related failures exist at newer fire sprinkler
installations. Ultrasonic testing at hundreds of building properties has
revealed wildly varying corrosion rates and remaining service life - which can
be often correlated to sprinkler pipe location, material, age, thickness
schedule, and most importantly, how often the pipe is drained and re-filled.
Each factor impacts fire sprinkler pipe significantly.

One major reason
for such problems is the more common use of thinner schedule 10 pipe, which
offers savings on both material and installation costs. Whereas extra strong
schedule 80 would have been typically installed 50-60 years ago, lighter
schedule 40 has been used since around the 1970's.
Over the past 20 years, this lite wall
schedule 40 pipe has been often replaced with even thinner schedule 10 -
leaving very little available pipe material to corrode before reaching minimum
acceptable thickness limits and the inevitable failure. For higher pressure
applications, schedule 10 pipe will provide acceptable service only assuming
that virtually no corrosion will take place - a known impossibility for steel
pipe containing water.
Where 8 in.
schedule 80 A 53 pipe having a wall thickness of 0.500 in. would have been
installed back in 1955, it is not unusual to find 0.188 in. thick schedule 10
installed today. This pipe offers less than half the wall thickness of schedule
80, as is shown in the below relative comparison, and will typically provide
10-20 years of service and little more, depending upon other factors related to
the operation of the system. Smaller diameter pipe has an inherently thinner
wall, and combined with any corrosion condition, can lead to a failure in as
little as 5 years or less.
|
|
|
Schedule 80 - 0.500
in. |
Schedule 40 - 0.322
in. |
Schedule 10 - 0.188
in. |
A default minimum
acceptable wall thickness of 0.100 in. exists for most steel fire sprinkler
service, or higher depending upon pipe diameter, pressure, and construction.
For 8 in. schedule 10 steel pipe, therefore, only 0.088 in. or less remains
available to corrode before reaching those minimum acceptable safe limits. At a
moderate corrosion rate of 5 MPY, the pipe will reach its minimum acceptable
thickness limit in roughly 17 years, whereas should a high loss MIC condition
develop having a 20 MPY rate, far less service life would exist.
See Technical Bulletin
# P-1 regarding minimum wall thickness calculations.

In most of our
ultrasonic testing investigations, we can demonstrate that the advanced failure
of a fire sprinkler system is directly related to water flow. Where the pipe is
filled, hydrostatically tested, and then left stationary, a certain amount of
corrosion takes places, the oxygen level is depleted, the lines remain
stagnant, and further corrosion virtually ceases. This is the most reasonable
explanation for older piping systems of the 1930's found in virtually new
condition today.
Where fire service piping
is frequently drained or the system often extended or modified, fresh new water
enters to greatly increase corrosion and pitting activity. In the worst of
examples, a constant flow of water may be present to create what is essentially
an open and chemically untreated condenser water system. This will occur where
small and unaddressed leaks exist to constantly bring in fresh oxygenated
water.
A frequently running jockey pump,
or cold sweaty fire sprinkler pipe are two sure signs of a leak somewhere
within the system. But while a leak within a building property is likely to be
addressed immediately, underground or other outdoor water loss problems are
often allowed to continue for years.
In
such cases, the greatest wall loss is typically found at the main line closest
to the water inlet due to the greater flow of water, and due to turbulence from
the city main, which introduces fresh oxygenated water. Lowest corrosion
activity, on the other hand, is typically found at the smallest diameter
sprinkler branch lines - this due to their existing in an essentially dead
ended and stagnant condition.
One sure
tell tale sign of a water influx into fire sprinkler pipe is a cold temperature
at the pipe surface, as a stagnant pipe should exist at ambient temperatures.
The rusted exterior of unpainted steel pipe, in the absence of high area
humidity and especially along the bottom, is another sure sign. Given enough
cold water flow, typically un-insulated fire sprinkler pipe will actually sweat
moisture condensation in the same way as an un-insulated domestic cold water,
chill water, or any other cold pipe
surface.
The below photographs offer the
type of evidence which often exists showing an active cold water flow. Similar
such evidence should always be investigated further.
|
 |
|
 |
Exterior Rusting - This fire
sprinkler pipe showed some mild general corrosion along its outer surface, and
a much greater amount of rust build-up at its very bottom.
Sufficient
moisture had condensed at the pipe to drip onto the below steam condensate
line, discoloring the fiberglass insulation. |
|
Moisture Condensation - Another
example where continued water flow through the fire sprinkler main pipe
produced excess moisture condensation at the surface.
Sufficient
moisture built up on the surface to drip on the sheetrock wall below and cause
discoloration. |
|

|
|

|
|

|
Two Problems - This fire sprinkler
pipe indicated a water flow condition due to the presence of condensation along
its exterior. In addition, the use of thin wall schedule 10 provided little
available pipe wall to corrode before reaching minimum thickness
limits.
While either condition will limit sprinkler pipe life, the both
combined virtually guarantee limited service. |
|
Cold Water Flow - Another example
of where a potential but hidden problem can be revealed by some close
observation.
Under no conditions would any stagnant piping system at
room temperature condense moisture from the air. Yet in this and other examples
we have seen, the presence of water droplets at fire pipe sprinkler pipe may
not be realized for its underlying threat. |
Perhaps the
strongest recommendation we can offer is to minimize the draining and filling
of any fire sprinkler system. This is difficult for modern office buildings,
however, where renovations and changes in tenants is frequent - prompting
piping changes and frequent draining and filling. Regular testing of the fire
sprinkler system, in itself and required by code, may also play a role in its
deterioration.

The quality of
the steel pipe is an important factor in fire sprinkler system corrosion as
well as for any piping application. While it is almost impossible to judge the
quality of a material source without first performing a metallurgical or salt
spray corrosion study (an unlikely event), accepting pipe from only known and
reliable sources is always a worthwhile recommendation. Seamed pipe should
always be avoided in favor of seamless
stock.
Whenever a corrosion problem is
identified at one pipe size but not at another, and given the absence of some
other factor such as additions to a specific fire zone or frequent drain downs,
the possibility that pipe from different steel mills, and perhaps different
countries, should not be excluded. The larger the installation, and the larger
the pipe size, the more likely different sources of material were used. Larger
size projects always favor lower cost pipe.

Dry pipe or
pre-action fire sprinkler systems are common wherever freezing is a concern,
where accidental water damage may occur, and for other engineering and design
reasons. With them, they bring new and typically unseen problems in the area of
corrosion activity.
While perhaps
"dry" in terminology, such fire sprinkler piping typically presents one
of the most corrosion susceptible environments for steel pipe due to the
moisture which inevitably remains within the system. A "dry" fire
sprinkler system may be drained after hydrostatic testing, but the water left
behind produces a moisture and oxygen saturated environment far more aggressive
against steel pipe than a completely water filled
system.
Proper pitch of the fire sprinkler
system is essential, but in reality, rarely drains the pipe sufficiently to
remove the moisture threat. For this reason, corrosion at the lower areas of
piping often exceeds the more elevated
areas.
To combat this problem, galvanized
steel pipe is often employed in dry systems, and will generally provide longer
service life strictly depending upon the quality of the pipe and strength of
the galvanizing finish. This benefit provided by galvanized pipe is
actually double edged. Once one or more areas of the galvanized finish fail, a
much greater degree of corrosive energy is focused on those select areas to
produce extremely high corrosion rates which can easily exceed 20 MPY, and
produce advanced failure.
|
 |
|
 |
Upper Rust Activity - This 15 year
old dry fire sprinkler pipe offers extremely little corrosion activity at the
top half or 12 o'clock area.
Ultrasonic testing showed wall thickness
values at or very near new schedule 40 pipe specifications, and visual
inspection shows the pipe in like new condition. |
|
Lower Rust Activity - The bottom
of the very same section of pipe at the left shows dramatically different
result. Pipe corrosion is heavy, resulting in tuberculation of the entire
bottom and lower sides.
Here , ultrasonic testing shows severe wall loss
and low thickness measurements at below minimum acceptable standards.
|
|

|
|

|
|

|
Corrosion Dividing Line - This
photo well illustrates the separation between virtually new pipe above the
water line, and shown at the left, and lower areas of the pipe left wet or
moist after testing, shown at the right.
Ultrasonic testing proved the
upper areas of the pipe in like new condition and suitable for decades of
further service, while the bottom of the pipe was found in imminent danger of
failure. Some of this particular section of pipe was removed due to pinhole
leaks. |
|
Cut Groove Failure - As is often
the case, multiple problems often exist simultaneously to greatly advance a
corrosion related failure.
In the other three photos of this set
representing investigation into the dry fire piping system, testing found wide
variance in condition based upon the pipe orientation. This problem becomes
more critical, however, given that the pipe groove is cut, and therefore
substantial pipe wall removed upon installation. |
While a corrosive
potential would be acting against the entire interior surface of a carbon steel
pipe, much of that same corrosive energy in a "dry" galvanized system is
now focused at a very limited surface area where the galvanizing finish has
been compromised. The result is typically pinholes through the pipe wall as if
produced by a drill bit, at the same time the overwhelming majority of pipe
wall remains at or near factory specification. Under such conditions,
galvanized pipe will actually fail sooner than standard carbon steel, where
corrosive attack is distributed over a larger surface area.

MIC has the
potential to virtually destroy an entire fire sprinkler system in just a few
years given corrosion rates which can exceed 50 MPY. Microbiologically
influenced corrosion is often suggested or mistaken for the more common
condition of simple under deposit corrosion, which can show similar
result.
Identifying an MIC condition
requires a thorough metallurgical and microbiological examination of a current
pipe sample. What causes MIC and how it can be prevented are less known. Since
it is biological, a through cleaning and sterilization of the pipe when first
installed is mandatory. Minimizing water flow through the system once placed
into service is another easy recommendation to offer, since the greater the
amount of water means the greater the potential microbiological source.
MIC presents a greater threat to
Victaulic or clamped joint piping systems due to the end to end gap which
exists for microbiological growth to accumulate and flourish. The threat of MIC
is so severe that once it is firmly established, most corrosion authorities
consider it impossible to correct in any piping system. A cut groove further
compounds the problem. See Technical Bulletin
P-3 about the threat created by cutting the groove for clamped pipe
construction.

But while a leak
at a fire sprinkler line presents the obvious problems, a further and often
unrecognized threat exists in the form of the iron oxide deposits created as a
result of the corrosion process. Such deposits can easily add up to thousands
of pounds of moveable rust debris capable of being dislodged from the shock of
a 150 HP fire pump kicking on, and moving downstream into the critical control
and actuating valves, and ultimately - the sprinkler heads.
Read a case history of
a sprinkler system that was clogged sufficiently by rust to block all water
flow during an actual fire
emergency.
A pipe testing
report showing a 40% average loss of wall thickness over 500 ft. of a 10 in.
schedule 10 fire sprinkler main would clearly explain the leaks and operating
problems experienced. Yet, that same 40% loss of steel from pipe which weighed
a factory new 21 lbs. per linear foot, also means that 8.4 lbs. of steel per
linear foot has now been removed from the pipe and placed into its interior in
the form of less dense iron oxide particulates.
For this 500 ft. fire sprinkler run, over
4,000 lbs. of steel can be assumed to exist inside the pipe in the form of both
hardened tubercular deposits and loose iron oxide mud - some of which will be
easily re-suspended during a fire emergency.
See Technical Bulletin
# M-15 regarding this hidden but often greater threat to fire sprinkler
systems.
Overall, new concerns
exist for fire sprinkler systems which seem to not have existed decades ago.
This demands much greater planning in their construction and maintenance, and
some form of corrosion monitoring to detect problems before they expand beyond
repair.
©
Copyright
|
|

|
|
|
|
|

|
|
|
 |
|
|