| |
|
 |
|
 |
|
|
|

|


The corrosion of
steel piping and its related components is a continuous and virtually
unstoppable process. Even with the application of available countermeasures,
pipe corrosion exists as one of the most potentially damaging threats to any
private, industrial, or commercial property - second only to
fire.
Corrosion activity affects HVAC
piping systems to varying degrees generally dependant upon the piping service,
quality of the steel, age, its size and layout, joining method, chemical
treatment protection, engineering design, and the specific corrosion mechanism
involved.
For many properties, the net
result is an added maintenance problem, greater energy costs, unnecessary
threat and liability, property damage, high remediation expense, and in the
most extreme examples - the need for partial or total pipe replacement.

Once established,
most corrosion conditions are difficult, if not impossible to eliminate or even
control. Repairs may be impossible and require total pipe replacement. Various
investigative resources are required in order to firmly identify the problem -
itself a major undertaking.
|


|

A very first step
toward resolving any corrosion problem is to establish the overall condition of
the piping system through a general ultrasonic investigation. Clearly
identified problem areas can then be further defined through the use of
metallurgical and microbiological analysis.
See Technical Bulletin
P-7 for more about the level of information provided by ultrasonic
testing.
By comparing
metallurgical against ultrasonic test results, it is often possible to identify
the extent and severity of the corrosion condition within the piping system.
Well documenting not only the corrosion mechanism itself, but the remaining
integrity of the entire piping system, is critically important in order to
minimize the potential damage from leaks caused by any planned corrective
actions.

Ten years of
experience in ultrasonic pipe testing at hundreds of commercial office
properties and plant operations has documented how environmental concerns and
government restrictions, combined with less tolerant engineering practices and
cost cutting, have greatly reduced the life expectancy of most new HVAC piping
installations.
Today's corrosion
inhibitors have proven to be less effective under real world operating
conditions when compared to prior chemical agents such as chromate and
hydrazine. Under low flow or dead end conditions, corrosion and pitting often
increases considerably. Whereas a 1 mil per year (MPY) corrosion rate for a
condenser water system could be reasonably expected decades ago, a 5 MPY rate
is now often considered acceptable, and costs significantly more to
achieve.
The greater corrosion
susceptibility of present-day steel pipe products is another major factor in
producing many high corrosion problems, and exists beyond any reasonable
control of the property owner or plant operator. With many foreign sources of
piping products well recognized for their lower corrosion resistance,
specifying domestic steel is strongly recommended - although offers no
guarantee of fewer problems.
Together,
these two elements alone can produce corrosion rates of above 25 MPY, which,
virtually unheard of 30 years ago, now offers the potential to destroy any
piping system within 10 years.

A major factor
seen at more recent commercial properties where piping failures have occurred
relates to the specified piping schedule. Most early U.S. office buildings
constructed prior to 1940 used extra strong pipe exclusively throughout. In the
1950's, thinner standard and schedule 40 pipe started being substituted for
less critical services such as chill water, fire sprinkler, drain lines,
domestic water, and secondary water systems.
From 1970 onward, extra heavy or schedule
80 stock might only be found at more critical and corrosion susceptible
condenser water and steam piping lines. Beginning in the 1980's, however,
virtually all building services piping, excepting those serving excessive
operating pressures, have been specified using standard or schedule 40
material.
This move by design engineers
and contractors from extra heavy to standard grade pipe has taken a further and
more risky step in the past 10 years with the use of thin wall schedule 10
steel in many fire sprinkler and condenser water systems - often with
disastrous results.


For a section of
8 in. condenser water pipe that would have provided an extra heavy wall
thickness of 0.500 in. for a 1950's property, or 0.322 in. at a facility
constructed of schedule 40 in 1985, the frequently seen use of schedule 10 now
provides only 0.188 in. of available wall thickness under substantially higher
corrosion conditions.
|
|
|
Extra Strong - 0.500
in. |
Schedule 40 - 0.322
in. |
Schedule 10 - 0.188
in. |

Not all piping
failures can be attributed to a high corrosion rate however. To a great degree,
many of the current problems seen at commercial office buildings and plant
facilities are simply age related. With many U.S. building properties reaching
40 years of service or more, the cumulative effects of even a moderate and
generalized corrosion condition will add up to produce substantial material
losses.
A low (and rarely seen) 1 mil per
year (MPY) corrosion rate at 12 in. schedule 40 condenser or chill water pipe,
while seemingly minor, actually results in the annual loss of 12.8 lbs. of
steel for every 100 linear feet of pipe. Multiplied by the number of years in
service and overall length - and the true magnitude of system corrosion takes
on much greater significance than when reported simply as 1, 2, or 5 mils per
year.
For a 40 story office property built
in 1965 and having 1,000 or more feet of 12 in. condenser riser piping, the
total loss of more than 5,000 lbs. of steel into the circulating system can be
shown. See the below table for the weight losses of various pipe sizes and
corrosion rates. See Technical Bulletin
# C-1 for the actual volume of rust deposits created.


Often, a low to
moderate corrosion rate will present no threat to the integrity of the pipe
itself, yet may still damage the piping system after many years or decades of
operation. At a constant 5 MPY corrosion rate, for example, 12 in. schedule 40
condenser water pipe will last well past 45 years before reaching 0.175 in. -
its minimum acceptable wall thickness under most conditions. Yet, that same 5
MPY corrosion rate still presents a very serious
threat.
Since the corrosion of steel
produces a significantly greater volume of less dense iron oxide, serious
secondary problems can be created unless such deposits are continuously
removed. Interior deposits can produce even more serious problems at closed
systems - where no blowdown exists and no indication is given. Corrosion
problems are often localized, and a gradual build-up of deposits in the lower
floor horizontal lines due to a low 1 MPY system wide corrosion rate can
produce random but severe wall losses at rates well above 25 MPY - leading to
premature pipe failure.

Unquestionably,
removing all existing deposits of iron oxide, which can total in the thousands
of pounds for even a medium sized commercial building system, should become the
most important focus in addressing any corrosion problem. Aside from lost heat
transfer, clogged strainers, and other operating problems, interior surface
deposits greatly accelerate pipe loss by preventing corrosion control chemicals
from reaching the base steel, and by initiating various secondary corrosion
mechanisms.

Due to the large
volume of deposits typically produced by any corrosion condition, the addition
of supplemental filtration is mandatory - with the option of filtering the
greatest possible volume of water preferred over capturing the smallest micron
particle. See Technical Bulletin
W-4 regarding various types of filters
available.
Chemically removing
the accumulated iron oxide by either dissolving it for blowdown or
re-suspending it for filtration capture is typically employed, but often
presents added threat to the piping and related system components depending
upon the remaining integrity of the piping, cleaning agent, and clean-out
procedure used.
Greater maintenance
demands in the form of punching heat exchanger tubes, cleaning strainers and
tower pans, and added filter maintenance may be temporary, or in the case of a
severe corrosion problem, may be a permanent addition to the operating schedule
of the property.
Increased chemical
inhibitor and biocide levels are generally required, as are supplemental
chemical dispersing agents. For a microbiologically influenced corrosion (MIC)
problem, repeated sterilization and cleaning of the system will be necessary.
Contracting an outside consultant to oversee and advise the chemical treatment
or cleaning program is often necessary due to the complexity of various
treatment options, conflicting claims and abilities of various chemical
treatment contractors, and the potential threat to the piping
system.
Under the most severe conditions
of a well established under deposit corrosion or MIC condition, it may be
impossible to save the piping system from premature failure. In such cases,
effort usually focuses on minimizing damage and operating problems, replacing
pipe as necessary, and extending its service life as best possible.

Avoiding such
corrosion problems from first developing is clearly desired. Strict attention
to the chemical water treatment through a reliable contractor is a high
priority - especially in the earliest days and months of the initial start-up.
Effective filtration and frequent cleaning of the piping system is mandatory,
as is careful monitoring for corrosion and biological
activity.
Corrosion coupons exist as the
most widely used form of corrosion measurement and monitoring today. However,
installed within an isolated loop separate from the many electrochemical
influences acting against the actual pipe surface, they at best offer an
estimate of the corrosivity of the fluid, rather than a true measurement of the
metal lost from the pipe itself. Read more about the
limitations of corrosion
coupons.
Corrosion coupons can
often produce falsely low corrosion estimates by a factor of 10 times or more,
and where significant iron oxide deposits exist at the pipe surface, will not
provide any indication of the deep under deposit pitting taking place.
CorrView ® monitors, removable spool pieces, and
ultrasonic testing, therefore offer better and more reliable testing options.
Maintaining trouble free HVAC piping
systems can be readily achieved, although not with the ease found decades ago,
and not without significantly greater expense and maintenance attention. New
influences at many different levels exist today favoring higher corrosion rates
- which must be recognized and effectively addressed by today's successful
building professional and plant manager.
©
Copyright
|
|
|
|
|
|
|

|
|
|
 |
|
|