| |
|
 |
|
 |
|
|
|

|


The most critical
piping for any building property or plant operation is unquestionably at the
fire sprinkler system. Corrosion problems at tower water, chill water, steam,
or other HVAC and plumbing piping may produce a loss of service, inconvenience,
property damage, shutdown, and even millions of dollars in monetary losses, but
the failure of a fire sprinkler line always threatens the loss of human life.
Often considered trouble free, corrosion
related failures at fire sprinkler lines have greatly increased over the past
decade - raising not only operating and repair costs, but the threat to
building inhabitants as well.

Unlike most HVAC
and industrial cooling applications, no chemical corrosion protection is
provided to the steel pipe which carries nearly all fire service water. This is
because traditionally, corrosion problems have not been a significant concern.
It is also due to the virtual impossibility of providing effective chemical
protection.
Up until 10-15 years ago, it
was almost unheard of for fire sprinkler pipe to fail, or to learn of sprinkler
pipe in need of replacement due to corrosion effects. This prior lack of
concern has changed in recent years due to the combined use of thinner gauge
pipe, seemingly more corrosion susceptible steel, to a higher frequency of
drain downs, testing, and modifica- tions to fire protection systems, and to
greater overall microbiological activity.
Corrosion rates which once could be
expected to range below 0.5 mils per year (MPY) for fire sprinkler lines two
decades ago, are now often measured at 5 mils per year and above.
See Technical Bulletin
# C-13 regarding the many corrosion factors affecting a fire sprinkler
system.

Many different
factors can lead to a corrosion problem at a fire sprinkler line. Absent or
improper chemical clean-out prior to beginning service may leave rust, metal
filings, mill scale, varnishes, iron oxide particulates, and foreign matter
behind to produce severe problems years later. The failure to disinfect the
pipe of micro organisms, combined with nutrients from any remaining organic and
particulate debris, can easily lead to an MIC condition.
A fire sprinkler system bringing in new,
fresh and oxygenated water on a regular basis is virtually guaranteed to
initiate severe corrosion problems. A frequently running jockey pump or make-up
water meter, or pipe which is cold and sweating, are two sure signs of a leak
or other flow problem.

It is a
correlation often unrecognized, but the presence of rust deposits at a pipe
surface define that a wall loss has occurred. Likewise, an identified wall loss
from an ultrasonic examination, defines that iron oxide deposits have been
produced. One condition cannot exist without the
other.
Exactly how much particulate debris
remains within the system is generally dependant upon the piping application
and any corrective measures applied. An open tower or condenser water line, for
example, will produce the same volume of deposits for the same MPY corrosion
rate as a closed chill pipe of the same size. However, a substantial volume is
washed out of the system during blowdown, filtration, and through regular
maintenance.
For open systems, the
presence of rust in the tower pans, strainers, and chillers, etc. is often the
first sign of a corrosion problem. Closed circulating systems typically hold
their deposits unless regularly flushed, or unless side stream filtration is
provided. Rarely opened for visual inspection, a loss of heat transfer
efficiency is often the first clue that an internal deposit problem exists.
But fire sprinkler systems provide a flow
of water in only one direction to multiple dead end branch lines, and lack the
benefit of circulation to move either cleaners or debris laden water to a drain
or into a filter for disposal. All iron oxide deposits, therefore, are usually
held captive within the piping. While flushing a fire sprinkler system might
show a limited benefit in removing some loose rust material over a limited
range of piping, it will not likely remove those heavier deposits under which
the highest corrosion and pitting activity always exists.

Minimizing the
actual threat of many corrosion problems is the misconception of exactly what
mils per year (MPY) means in terms of wall loss. Different authorities may
provide recommended acceptable wall loss estimates in MPY, but the true impact
of that pipe loss is rarely understood or appreciated in real world
terms.
A corrosion rate of 5 MPY is
obviously worse that a 2 MPY rate, but to what degree in terms of pipe service
life and volume of deposits produced? A low corrosion rate of 1 MPY at a 10 in.
fire sprinkler main, for example, while it would be viewed as acceptable by
most authorities, actually translates to an annual physical loss of 11 lbs. of
steel for every 100 linear feet of pipe.
At 10 MPY, approximately 107 lbs. of
metal is lost. Multiplied by the number of years in service and its overall
length, and the true magnitude of pipe corrosion takes on much greater
significance than when reported as simply 1, 2, or 5 mils per year. The below
table illustrates just how much steel is lost at various corrosion rates and
for various pipe sizes, and is applicable for any piping system.



But while even a
5 MPY loss of metal can be tolerated by many piping systems for an extended
period of time before resulting in a leak, it is the deposits created, and
their eventual deposition and effect, that will inevitably produce far more
serious and long term secondary problems.
Steel, when corroded back into iron
oxide, produces a significantly greater volume of less dense material by a
factor of approximately 18-20 times. Such deposits, in turn, ultimately create
a substantial loss of heat transfer efficiency, constricted flow, and under
deposit pitting and wall loss. At a low corrosion rate of 1 MPY for an office
building having 40 floors of 24 in. chill water piping, 242 lbs. of steel will
be lost for each year of service at just the risers alone.
In its less dense form of iron oxide,
however, this same steel will exist having a volume of 10 cubic feet. See the
below table for rust volumes produced for other corrosion rates and pipe
sizes.


After 20 years,
and where no chemical cleaning or filtration had been provided, it would be
easily possible to accumulate 200 cubic feet of rust deposits at points within
the system - often at heat transfer surfaces.

It is important
to recognize that all carbon steel pipe will corrode to some degree. Even when
chemically protected, pipe corrosion can only be minimized, never stopped. With
the application of chemical corrosion inhibitors generally not feasible for
fire sprinkler service, the rate of its inevitable deterioration becomes
generally dependent upon certain fixed parameters.
Of first importance is the amount of
fresh water entering the pipe - with highest corrosion rates consistently found
where water flow is the greatest, such as at the inlet.
A second critical factor is pipe
schedule. At any given corrosion rate, the service life of a pipe before
failure is directly dependant upon its initial wall thickness. For this reason
alone, far more sprinkler failures occur today due to the common use of thin
wall schedule 10 pipe. Schedule 10 offers savings on material, time, and
installation costs, but at the trade-off of severely reduced service life.
Whereas extra strong schedule 80 would
have been typically installed 50-75 years ago for fire service, lighter
schedule 40 has been used since around the mid 1960's. Over the past 20 years,
this thin wall schedule 40 fire pipe has been frequently replaced with even
thinner schedule 10 - leaving very little available pipe wall to corrode before
reaching minimum acceptable thickness limits and inevitable failure.
The below comparison of 8 in. ASTM A53
black pipe shows the representative amount of available wall thickness that
would be available to corrode at a sprinkler line installed decades ago using
schedule 80, as opposed to most new installations today using schedule 10.
|
|
|
Schedule 80 - 0.500
in. |
Schedule 40 - 0.322
in. |
Schedule 10 - 0.188
in. |
Under the clearly
greater overall corrosion threat which exists today, only 0.088 in. exists to
corrode before this schedule 10 pipe will reach minimum acceptable standards.
For higher pressure applications having a higher minimum acceptable thickness
limit, schedule 10 pipe will provide service only assuming that virtually no
corrosion will take place - a known impossibility.

The ultimate
impact of internal deposits, similar to wall loss itself, is greatly dependent
upon the piping system involved. Deposits produced at an open piping system
will be observed quickly and be likely addressed, while a closed system will
instead conceal is problem until a heat transfer loss, leak, or some other
operating problem is realized.
But
corrosion at a fire sprinkler system is often totally concealed from view, and
may remain unrecognized for years. No external signs or indicators normally
exist to suggest a corrosion problem prior to a leak occurring - at which time
the major damage, often irrevocable, has already taken place.
Ultrasound, which is unquestionably the
most cost-effective nondestructive technology available to detect a corrosion
problem in pipe, is rarely used as a preventative tool in evaluating fire
sprinkler systems. See Technical Bulletin
P-7 regarding the benefits of ultrasonic pipe testing.
In most cases, the concern raised due to
a leak at fire sprinkler pipe is more directed to the potential for water
damage or cost of replacement, rather than whether the pipe will provide the
necessary water flow during a fire emergency. And yet the latter, by far,
presents the greatest threat.

In fact, years of
corrosion activity can easily produce thousands of pounds of debris capable of
being dislodged from the shock of a fire pump kicking in, and then forced
downstream into the critical actuating valves, and ultimately - the sprinkler
heads. At that point, all the fire fighting equipment, command and controls,
sensing, planning, inspection, and emergency training suddenly becomes
worthless if water cannot be supplied to the source of the fire.
Read a case history of
a sprinkler system that was clogged sufficiently by rust to block all water
flow during an actual fire
emergency.
The potential for
such a catastrophe is easily demonstrated. A 25% wall loss at an 8 in. schedule
10 sprinkler main, for example, is still not likely to produce any notice in
the form of a leak or failure. Yet, that same 25% loss of steel from pipe which
weighed a factory new 17 lbs. per linear foot, also means that 4.25 lbs. of
steel per linear foot has now been removed from the pipe, and placed into its
interior in the form of less dense iron oxide particulates.
For a 600 ft. main sprinkler feed, it is
easy to estimate that 2,500 lbs. of rust would now exists in some proportion of
hardened deposits or tubercles attached to the pipes interior wall, and
the rest as loose sediment and mud along the bottom. This material accumulates
with time, ultimately to the point where the pipe wall finally fails and brings
attention to the problem, or to when a fire occurs.
In a very possible worse case scenario,
this loose rust and mud will be dislodged by the shocking action of the fire
pump starting up in response to a fire call. With perhaps thousands of pounds
of loose material suddenly rushing downstream toward the fires location,
the potential to block closed any control or preaction valves, reducers, tees,
small diameter distribution lines, or fire sprinkler heads is tremendous.
Such an actual event, whereby the fire
sprinkler lines have been found totally clogged with rust and mud in a fire
emergency, has actually occurred in previous instances - leaving those involved
without the fire protection they believed existed.
|

|
|

|
You
can download and print out a condensed two page handout on this subject in
Adobe PDF format from our Documents download
page, or view the full article by clicking the image at the
left.
We offer certain topics and some of
our Technical
Bulletins in condensed format for your conveniece. Further documents
will be added as time allows. |
|

Such severe
corrosion problems have been commonly attributed to microbiologically
influenced corrosion, or MIC. But while MIC may exist as the foremost cause,
the end product of MIC and the source of sprinkler failures, rust deposits, can
be produced by various other corrosion mechanisms.
Common to all problems, however, is the
infiltration of fresh water into the system. If filled and left stagnant, a
small amount of rusting occurs, the oxygen content is depleted, and corrosion
almost ceases. In contrast, the constant renovation and upgrading of newer
properties itself promotes fire sprinkler problems - as every draining and
refilling introduces into the pipe new oxygen, biological sources, as well as
the nutrients they need to thrive.
Ironically, one of the root causes of the
greater fire sprinkler problems seen today is mandated proce- dures to ensure
their proper operation in the first place. Each required test of a fire
protection system intro- duces new fresh water to produce further
deterioration.
With so many forces acting
against modern fire sprinkler systems, and few protective measures available,
better corrosion monitoring becomes the only means to ensure that water will be
available when a fire emergency exists. You can download a 2 page Adobe PDF
handout on this subject from our Downloads
Page
©
Copyright
|
|

|
|
|
|
|

|
|
|
 |
|
|