| |
|
 |
|
 |
|
|
|

|


It would be
impossible for a failure at a section of main condenser water riser to go
unnoticed for more than a few minutes. A blown off fitting at even a 1 in.
medium pressure line would produce hundreds of gallons of water - causing it to
be quickly located and addressed. In contrast, much smaller leaks, depending
upon their location and severity, can produce severe secondary problems that
can easily avoid detection. In certain instances, a smaller leak can actually
create greater damage than one which is much
larger.
A leak at a threaded connection,
often the very first sign of a pipe corrosion condition, may exist for years
prior to producing enough water to signal a problem. Often located behind
walls, in shaftways, under floors, and above ceilings, thread joint failures
can slowly leak water into area surroundings to corrode other piping systems,
metal supports, electrical services, and other equipment. The extent of the
damage is usually detected only once the leak extends past its immediate area
and into the view of others.

Just what extent
of damage occurs is often related to where the leak exists and how far the
water travels. A small leak at a vertical riser, and especially where the shaft
is open floor to floor, can produce extensive damage for hundreds of feet as
the leak slowly descends the pipe. In contrast, piping shaftways having a
firestop at each floor will typically show signs at that floor as the water
expands on that level only.
If the pipe is
insulated, the insulation material will often collect the water to the point
where it is completely waterlogged, thereby producing an exterior pipe
corrosion problem along its entire outer surface. Even a small to moderate leak
at one location can saturate multiple floors of piping to produce an extensive
degree of outer wall loss. Given enough travel, it will evaporate along its
path and still not produce a tell tale indication.
Leaking pipe at a vertical riser often
deteriorates the steel pipe supports at the floors to the extent of making them
virtually worthless. This creates added stress on existing supports, and
increases the threat of pipe separation - especially if the pipe is joined by a
means other than welding.
An extremely
common problem exists where a leak occurs over an electrical service panel or
conduit. Given the typically thin gauge of such enclosures, a few years of
constant moisture is all that is necessary to produce a penetration through the
metal - allowing water to contact the energized electrical components, and to
eventually short the wiring.
Some common
problems related to water leaks are presented below, and help to underscore the
often unseen or unexpected threat which water can bring:

|

|
|

|
Electrical Threat - An electrical
service riser in this shaftway was installed immediately next to the condenser
water riser. In addition, the take-off from the riser to floor units ran
parallel and above the electrical box and conduit.
As a result of a
moderate corrosion rate of 4 MPY over a decades, and galvanic activity between
the black steel pipe and brass valve, the schedule 40 pipe began leaking at the
threads to corrode the junction box and cable below. |
|
Common Pump Problem- All pumps
offer a catch basin below the seals to collect any water lost. These basins are
often piped into the lower trough and then routed to drain.
Water then
typically collects to initiate a corrosion problem between pump base and stand.
Once rust develops, it will slowly expand and actually raise the pump upward,
causing it to lose alignment and stressing the bearings and seals to produce
greater leakage.
This can be avoided instead piping the seal basins
directly to the drains. |

|
 |
|
 |
Moldy Insulation - Sometimes due
to a leak, but often due to cold water condensation alone, moldy insulation
will result if given the proper conditions.
This problem is easily
recognized by the dark discoloration of the insulation, but where concealed out
of view, can grow into an extensive problem. Combined with a movement of air to
carry the mold spores, this water related problem has been the cause of many
toxic outbreaks nationwide. |
|
Hidden Pipe Leak - A small pinhole
leak at a threaded fitting 15 floors above ran down the pipe unnoticed until
finally reaching this lowest floor apartment.
This problem was first
addressed by painting the ceiling over and over. Given enough time, the leak
caused extensive outer pipe damage and further failures along its 15 floor run.
Ultimately, some lengths of pipe were replaced as well as much of this
ceiling. |

|
 |
|
 |
Electrical Failure - A small leak
at a threaded elbow within a ceiling area allowed water to drain to its lower
horizontal line. Water collected at the insulated pipe, where it severely
deteriorated the water line (shown at top).
Water dripping from the
insulation onto a 480 volt electrical conduit below eventually corroded the
line completely through in areas to create a new threat to other building
services and potential for fire. |
|
Deep Pitting - A small leak at a
threaded air vent to this domestic hot water tank went unnoticed for many
years, leaking under the hard cast insulation along a major portion of the tank
shell and then evaporating.
When finally discovered, wall loss of over
0.250 in. was measured at the tank's outer surface to leave a suspected 0.030
in. or less in some areas, and repair was recommended. Failure at the above
area occurred six months later and before repairs could be performed. |

|
 |
|
 |
Exterior Corrosion - A small leak
at a weld for this low pressure domestic hot water tank was concealed by hard
shell insulation for years. This produced severe pitting in this localized area
of approximately 0.225 in. deep.
Sufficient wall thickness existed at
this head to provide additional service life. The head was cleaned of all rust
product and a repair patch welded over the entire area. |
|
Condensation - An unknown
condensation of moisture at the very bottom of this refrigeration machine
evaporator produced a severe and localized corrosion. After 15 years, corrosion
produced pinholes through this relatively thin 0.125 in. steel
shell.
More severe wall loss was produced between the bottom of the
evaporator shell and metal base support, requiring removal and
repair. |

|
 |
|
 |
Insulation Mold - Poorly insulated
chill water pipe having frequent gaps at the seams, and in the presence of a
high humidity environment, produced extensive mold throughout the entire
system.
UT testing showed surprisingly little corrosive effect against
the exterior pipe wall, but overwhelming health threat due to widespread
mold. |
|
Insulation Mold - Poorly insulated
chill water pipe having frequent gaps at the seams, and in the presence of a
high humidity environment, produced extensive mold throughout the entire
system.
UT testing showed surprisingly little corrosive effect against
the exterior pipe wall, but overwhelming health threat due to widespread
mold. |

In most cases,
secondary corrosion problems only exist where the wrong combination of factors
occur - either because they are overlooked, or occur in a hidden environment
and out of view. A minor drip allowed to continue might not mean anything in an
open area of a floor drain, but will produce significant damage within an
enclosed space.
A pipe with wet insulation
may not be any threat at the roof level cooling tower, but where it exists in a
dark damp environment such as a fan room, raises the potential to grow and
distribute mold spores throughout the entire facility. Prompt attention to
maintenance is always recommended.
©
Copyright
|
|
|
|
|
|
|

|
|
|
 |
|
|