| |
|
 |
|
 |
|
|
|

|


Over the
life-span of any building property or plant operation, the replacement,
renovation or addition of various piping systems is a frequent occurrence. Due
to the fact that operating pressures of most high rise buildings or process
plants rarely exceed 300 PSI, internal pressure does not often factor in the
selection of pipe schedule.
Today,
schedule 40 black pipe is almost automatically chosen for most small diameter
piping needs - with little thought given to the physical wall thickness
limitations of the pipe itself. High pressure steam and other critical services
are the exception. As a result, it is not uncommon to find the premature
failure of relatively new condenser or process water installations, as well as
examples of properties which have replaced such small diameter piping on a
regular basis every four, five, or six years.

In contrast,
piping systems decades older often provide significantly longer service life.
This is in part due to the previous use of schedule 80 or extra heavy pipe for
all threaded applications. Other factors such as better quality steel and more
effective chemical corrosion protection of years ago also play an important
role, but it is the thinner pipe wall thickness used at installations within
the past 25 years which often becomes the most important limitation to long
service life. Review a summary of
piping quality, operating, and design changes which have
occurred.
Allegations of poor
or unsatisfactory chemical water treatment is almost immediately cited in such
failures, although for most cases, testing will show an acceptable to moderate
corrosion rate. In fact, the problem commonly exists because more than 50% of
the original pipe wall is removed in the threading process, leaving little
material remaining. Joint compounds and sealants, and/or the degree to which
the connection is tightened, are rarely capable of holding back water once the
threaded wall area is penetrated by corrosion.

The below table
well illustrates the degree to which the threading process weakens schedule 40
pipe - a loss rarely considered by building engineers, plant operators, and
many mechanical contractors. A consulting engineer or mechanical designer will
often initially specify schedule 80 or extra heavy pipe as soon as threading is
involved, but such plans then change at some point along the way toward
installation. Cost cutting, or reducing the pipe thickness based on pressure
requirements alone, are typically the reasons.
At the smallest sizes, the amount of wall
lost during threading actually equals approximately 65% of the original pipe
wall. Such initial high wall loss, coupled with a corrosion rate anywhere
exceeding 2 MPY, will inevitably produce a premature pipe leak.



The long
established standard piping formula, known as the Barlow formula, (Piping
Handbook, Nayar, 6th Edition, C.138) is used to calculate the pressure that a
section of pipe of known thickness will tolerate, and is represented as:
tm = PD/2SE + A
This formula
takes into account variances in:
- Pipe diameter
- Internal
pressure
- Material stress
factor
- Temperature
- Corrosion
allowance
- Mill tolerance
- Material
strength
- Joint
preparation and efficiency
The minimum wall
thickness derived by this calculation is relevant for all types of pipe, as
well as for all materials, and is the standard by which design engineers
specify the materials for new building or process piping
construction.
In general, schedule 40
steel piping satisfies the engineering requirements of most building
applications. However, under certain conditions and pipe sizes, special
consideration must be taken to ensure that threading or grooving does not
reduce the pipe wall thickness past the permissible minimum dimensions. With
threaded schedule 40 pipe used in condenser water or open process applications,
that minimum acceptable wall thickness standard is not met for most small pipe
sizes on the first day of installation.

For illustration,
CVI has prepared the following table showing a series of calculations for
carbon steel black pipe in sizes 3/4 in. through 3 in. Different configurations
of schedule 40 vs. schedule 80, open vs. closed, and welded vs. threaded pipe
are presented.
At the two far right
columns comparing both new original pipe wall thickness and calculated minimum
acceptable wall dimensions, we can easily illustrate the threat of using
schedule 40 pipe under certain operating conditions. While corrosion activity
is still the major factor in piping failures, in fact, even new schedule 40
pipe does not meet minimum minimum thickness requirements in threaded open
water applications based upon the minimum value calculated according to Barlow.
In such applications, therefore, the use of schedule 80 is recommended.


We can see by
both piping tables that the primary cause of failure to meet minimum
specifications is the amount of wall thickness removed in the threading
process. Secondary to that is the higher corrosion rate factor specified for
open water condenser systems - a 0.065 in. lifetime corrosion allowance we have
well documented as being far too low for today's operating conditions.
This 0.065 in. wall loss was factored
into the Barlow formula based upon anticipation of a low 1 MPY corrosion rate
over the 65 year estimated service life for a typical building property. With
3-5 MPY being more the average condenser water corrosion rate today, and with
10 MPY corrosion rates not uncommon, it is in fact possible to exceed this
previously anticipated lifetime corrosion loss of 65 mils in only a few
years.
CorrView International has long
used the Barlow formula in all ultrasonic piping investigations, and has found
the resulting minimum acceptable wall thickness and remaining life prediction
estimates accurate and reliable. It is the firm recommendation of CVI that
schedule 80 black iron pipe should be used exclusively under such threaded
condenser water conditions - regardless of operating pressures. Its use in
other services where small diameter piping exists provides an added level of
protection.

The below sample
of new 2 in. threaded ASTM A53 pipe very well illustrates the high degree of
wall loss caused when pipe is threaded. Such thread loss is unavoidable in most
circumstances, but where installed in more corrosive environments, must be
compensated for by using heavier materials if long service life is
desired.
|

|
This above
cross sectional close-up view of a threaded end of schedule 40 pipe shows the
original wall thickness at the left having a micrometer and ultrasonically
measured wall thickness of 0.156 in. - just slightly above the ASTM factory
specification of 0.154 in. This cross section of a standard NPT taper thread
shows the deep loss of steel at the right side or forward edge of the
thread.
We can provide another close-up
view of the same pipe sample below, and again showing the cross sectional area
lost due to threading.
|

|
Here, a
micrometer measurement at its solid wall thickness dimension shows 0.156 in. of
available pipe wall, while the below photograph taken at the lowest cut area of
the threads provides only 0.079 in. of pipe wall. This represents a 0.069 in.
or an approximate 50% loss which occurs on the first day of
installation. |

|
It is this
high initial wall loss, ranging from 35% to 68% of the original schedule 40
pipe wall, which typically limits the service life of any threaded piping
system. Schedule 40 pipe typically does not provide condenser water service
much beyond 15 years except at the most well maintained systems - where
corrosion can be confirmed at 1 MPY or below. With 0.069 in. of material at its
leading edge, and having a more typical corrosion rate of 4-5 MPY, it is easy
to demonstrate that a service life of 10 years or less is all that should be
expected from schedule 40 condenser water pipe. |

Failures at
threaded joints represent the most common of all corrosion related problems.
The appearance of a leak is rarely an isolated event, but simply the first
indication of a larger and system wide problem. While spot repairs may extend
the service life of the system, at some point the increased frequency of
failure will demand total pipe replacement. As the piping system is allowed to
operate under such conditions, the level of threat for a major piping failure
also increases.
The below photo gallery
illustrates the typical evolution of a threaded joint failure at steel to steel
connections. Under the same corrosion characteristics, threaded joints will
always fail prematurely. In many examples, this loss is amplified by galvanic
activity caused by the direct connection of threaded black pipe to a brass
valve or copper fitting. See Technical Bulletin
P-10 regarding galvanic corrosion.

|


|

What appears in
the above photo gallery as a corrosion problem originating at the outside of
the pipe is actually the beginning of a small leak. Dissolved iron oxide, fine
particulates, calcium carbonate and other water soluble elements are carried
through the microfine penetration of the pipe to the outside and evaporate.
These dissolved elements then precipitate out and accumulate at the immediate
area. As long as the rate of evaporation exceeds the rate of the leak, the
problem remains localized.
Such small
leaks are often not noticed or simply ignored. Once the leak rate exceeds the
evaporation rate, however, water droplets travel elsewhere to cause additional
problems, and repairs are required. Ignoring such small tell tale signs of a
problem allows a greater amount of the pipe to wear - thereby possibly creating
a much greater leak once it does eventually fail. The common argument that pipe
leaks seal themselves up with internal rust simply does not
hold.
The use of schedule 40 threaded pipe
at fixtures such as temperature wells, pigtails, pressure gauges, and control
sensors also presents the same threat. If located before a shut-off valve, the
failure of even such small piping components can require the shut down of the
entire piping system for repair.

Under controlled
corrosion conditions of 1 MPY of less, such as occurs typically at chill water
systems and other closed conditions, threaded schedule 40 pipe offers generally
acceptable service life. Yet, under extremely high corrosion conditions, the
installation of threaded schedule 40 pipe can produce failures in as little as
two years.
It should be noted that while
schedule 80 pipe does provide greater wall thickness and therefore greater pipe
life, it does not offer substantially longer service life under high corrosion
conditions exceeding 10 MPY. Brass valve to carbon steel connections lacking a
galvanic coupling or insulator, a common installation scenario, simply
accelerate the corrosion process.
In
short, a high corrosion condition is a problem - but a high corrosion condition
where threaded schedule 40 pipe has been installed represents significantly
greater threat, and difficulty to correct.
Under controlled
corrosion conditions of 1 MPY of less, such as occurs typically at chill water
systems and other closed conditions, threaded schedule 40 pipe offers generally
acceptable service life. Yet, under extremely high corrosion conditions, the
installation of threaded schedule 40 pipe can produce failures in as little as
two years.
It should be noted that while
schedule 80 pipe does provide greater wall thickness and therefore greater pipe
life, it does not offer substantially longer service life under high corrosion
conditions exceeding 10 MPY. Brass valve to carbon steel connections lacking a
galvanic coupling or insulator, a common installation scenario, simply
accelerate the corrosion process.
In
short, a high corrosion condition is a problem - but a high corrosion condition
where threaded schedule 40 pipe has been installed represents significantly
greater threat, and far more difficulty and expense to correct.
©
Copyright
|
|
|
|
|
|
|

|
|
|
 |
|
|