| |
|
 |
|
 |
|
|
|

|


Throughout the
history of most building properties and plant operations, some degree of
corrosion at the outside surface of the chill and cold water piping will occur.
Surface pipe corrosion can range from cosmetic and mild, to severe and system
debilitating. Corrosion under insulation, CUI as it is known, is generally a
long term problem taking decades to develop. This partially explains its low
priority in most building and plant maintenance plans and
procedures.
The presence of condensation
at the outer pipe wall produces much the same corrosive effects typically
associated with interior pipe corrosion, except that microbiological attack
rarely occurs. In extreme cases, condensation will build up to the point where
the insulation becomes completely saturated with water. Generalized corrosion,
excess surface pitting, as well as the deterioration and failure of the
insulation itself, usually results. Although presumed to be a long term
problem, under certain conditions, exterior corrosion can produce noticeable
effect within 10 years.

While fiberglass,
foam, and other forms of insulation serve to provide important protection
against unwanted heat transfer, their equal or more important function for cold
water systems is to prevent the migration and condensation of moisture onto the
outer pipe surface. Such function is rarely considered, however, in the
selection of cold water piping insulation, and standard insulation tables
provide recommended thickness values dependent mostly upon pipe diameter.
The thinner the insulation, the greater
the transfer of both heat and moisture to the pipe surface, and therefore the
greater the resulting corrosion problem. Even installing 2 in. or thicker
fiberglass insulation, although excellent at reducing heat transfer losses, is
often not itself sufficient to prevent the infiltration of moisture and
condensation at a cold pipe
surface.
Moisture easily migrates to the
surface of the smaller diameter piping - where multiple turns, connections, and
fixtures such as valves, strainers, and gauges make an effective insulation job
difficult, if not impossible. Any crack or sealing failure then becomes an
entry point for moisture to permeate under the insulation and travel along the
pipe surface for significant distance.
In
many examples, therefore, the larger diameter main piping will show little or
no surface deterioration, whereas the smaller distribution and run-out lines
will rest near the point of failure. Identifying small diameter pipe where
corrosion has completely worn away the exterior threads is not at all
unusual.
The previous use of hard formed
insulation, decades ago, was extremely effective at isolating the cold pipe
surface from outside moisture. Commonly used fiberglass insulation of today,
which offers a semi-permeable cloth or paper outer covering, provides no real
moisture barrier, however, and requires additional steps such as coating or
painting over the insulation in order to stop a corrosion problem. Other
preventative steps are also often necessary.

For inside
locations, exterior corrosion is dependent upon a combination of the thickness
and condition of the insulation, the water temperature, and the relative
humidity in the area. Generally, corrosion will be much more severe at the
supply side piping simply due to the presence of lower pipe surface
temperatures - typically lower by a factor of 10 º F.
Depending upon the humidity level
present, it is not unusual to find a 55 º F. chill water return line free
of any surface corrosion while the 45 º F. supply side pipe has been
severely pitted and deteriorated. Likewise, the same chill water supply line
may show high pitting in a more humid mechanical room or steam room area, and
none at all once it passes into an air conditioned tenant space having less
relative humidity.
Brine and ammonia
refrigeration systems, or those operating at 35 º F. and below, are most
susceptible to outer surface corrosion. Heavy insulation to limit the travel of
moisture, and a strong preventative coating at the pipe itself to serve as a
moisture barrier, are necessary to counter the threat from such low
temperatures.
The humidity level is often
the most critical factor, and we have documented condensation and the complete
destruction of condenser water pipe at 95 º F. where it has traveled
through a heavily moisture saturated steam station area. The higher the
moisture content, the less cold is needed to create an exterior corrosion
problem.

Unlike interior
pipe corrosion which can never be stopped, and which exists due to a complex
variety of physical and chemical causes, piping failures due to the extreme
outer corrosion of chill and cold water systems are almost totally preventable.
Such failures are generally attributed to inadequate or neglected maintenance,
and/or the failure to inspect for and recognize such corrosion
problems.
Chill water pipes are not the
only victims of such outer surface corrosion. A common occurrence in steel
domestic house tank evaluations is to find extreme outer corrosion at the
bottom or underside surfaces. Here, inaccessibility often prevents adequate
coating or painting. For the same reason that it is out of sight and therefore
out of mind, normal maintenance to the side walls is rarely performed at the
bottom surface. See Technical Bulletin
C-6 for more information about corrosion at domestic water
tanks.
The below photo gallery
dramatically illustrates the ultimate consequence of inadequate pipe insulation
and/or maintenance.

|
 |
|
 |
Exterior Wall Loss - This 1-1/2
in. Schedule 80 black pipe chill water supply line was identified as having an
outer corrosion rate of approximately 4 times that of the water side, and an
existing wall thickness well below minimum acceptable standards - at
approximately 0.089 in.
All evidence of threads, 0.073 in. deep for
this size pipe, have been completely corroded away. |
|
Slow Deterioration -
25 years of high humidity conditions effectively penetrated the insulation to
slowly cause a severe external corrosion condition. Extensive rust removal,
painting, and re-insulation was required.
Surprisingly, sufficient
remaining wall thickness yielded an acceptable remaining service life of 25
more years at this 8 in. chill pipe. |

|
 |
|
 |
Generalized Corrosion - Severe
external corrosion actually produced a uniform layer of rust product of
approximately 1/2 in. thick. In this case, a general ultrasonic piping
evaluation discovered this condition, as well as showed it was a uniform loss
and not a pitting condition.
Acceptable wall thickness remained and the
pipe was coated and re-insulated. |
|
Condensation - This shows the very
early stages of a future external corrosion problem. Here, the use of 1 in. of
fiberglass insulation over a 12 in. chill supply pipe at 44 º F. almost
totally saturated the insulation with water in only 5 years.
Random
areas of mild corrosion were found and re-insulation with heavier material was
performed. |

|

|
|
 |
Deep Pitting - Corrosion from
exterior sources can take the route of general corrosion to deep localized
pitting - similar to interior pipe problems. 10 years of service at this
Ammonia plant produce random and deep 0.150 in. pits along the top of this
pipe. |
|
Small Fixtures - Small pipe
fixtures such as pressure and temperature gauges, and instrument transmitters,
are at special risk. This is due to the difficulty of insulating them, their
inherently thin pipe wall, and to losses suffered when threaded. |

|
 |
|
 |
Failed Insulation - Cold water
piping will attract area moisture through any paper or cloth covered insulation
to condense on its surface. Once saturating the insulation itself, the moisture
will often produce droplets at its exterior. |
|
Waterlogged - Opening chill water
insulation, where the insulation has failed, will often reveal a saturaged
interior. This water content represents an untrested water condition to the
pipe exterior, and wil inevitably cause failure. |

|
 |
|
 |
Insulation Failure - Under
insulation corrosion is often due to a combination of insulation failure itself
and cold pipe temperatures. It may also be due to insulation failure alone -
which is an important distinction.
A greater threat exists for cold
water pipe since insulation damage is not necessary, nor is the corrosion
limited to any local area as shown above. |
|
Tank Corrosion - Most cold
domestic water tanks suffer a similar condensation problem at their outer
surface, and especially at the lower areas and bottom of the tank where the
cold water stratifies.
Protection of the tank is entirely dependant on
coating effectiveness, and severe pitting can occur of not addressed
appropriately. |

|
 |
|
 |
Random Deep Pitting - Pitting
offers much greater threat since the corrosion activity is focused against
specific areas like a drill bit - rather than the entire surface.
Whereas a generalized exterior corrosion rate of 2-3 MPY can often be
tolerated, a pitting rate of 10-15 MPY will certainly produce a piping failure
if undetected or ignored. |
|
Foam Insulation - Severe corrosion
activity is well known to occur under closed cell foam piping insulation. Such
is often used to protect the smallest runout piping and small fixtures.
No clear reason is understood, but under certain conditions, foam
insulation seems to react with steel and copper to produce the above
result. |

|
 |
|
 |
Return Side Corrosion - This set
of photographs offers a good side by side comparison of the much greater damage
to supply side chill water piping which normally occurs when the insulation is
inadequate, and surface temperatures sufficiently cold.
This set of
supply and return pipes existed parallel to each other and are identically
insulated, yet the return side pipe shows much less exterior corrosion.
|
|
Supply Side Corrosion - The supply
side pipe of the chill water loop shows severe pitting, with an estimated depth
of penetration into the pipe of about 0.150 in.
Given that this is only
2 in. extra heavy pipe having a measurable remaining wall thickness in other
areas of under 0.200 in., no possible service life remains. Ultrasonic testing
cannot be performed due to its rough surface conditions. |

|
 |
|
 |
General Neglect - This chill water
main supply pipe, located in a steam station area, showed a severe
deterioration due to a complete lack of insulation in many areas.
Building management contracted ultrasonic testing in order to determine
its condition, and when found to still have an acceptable wall thickness, rust
removal, painting and insulation plans were abandoned. |
|
Imminent Failure - Such small pipe
sections are always at the greatest threat. They are the most difficult to
insulate, have gaps for air to easily infiltrate, and are usually insulated
with very thin materials.
In addition, more than 60% of the original
pipe is usually cut away while threading, which is usually for the purpose of
attaching a brass valve - a source of galvanic activity. |

|
 |
|
 |
Waterlogged Insulation - A good
view of water saturated fiberglass insulation. This recently installed chill
water piping was found to have the beginning of a serious exterior rusting
problem after only one year in service.
Found at its beginning stages,
mostly in the more humid mechanical areas, painting and re-insulation was the
only option. |
|
Rust Layering - Like interior rust
deposits, corrosion created by a water condition at the exterior of a pipe
often results in a buildup of multiple layers of rust.
In most cases
this represents a general or milder wall loss - which is actually preferable to
pitting type exterior corrosion which produces deep and localized
deterioration. |

|
 |
|

|
Waterlogged - Very severe exterior
corrosion was found under previously installed fiberglass insulation after 25
years. The pipe was re-insulated with foam insulation as a suggestion to better
prevent moisture condensation.
Following two weeks of operation, the
foam insulation was opened and found to be completely flooded with water.
|
|
Missing Insulation - A not
uncommon problem often caused by the difficulty in insulating certain piping
areas. Here, straight runs of pipe were insulated while elbows, tees, and
valves were not.
Relatively minor rust was found under the insulated
pipe, but bare sections showed high corrosion and moderate pitting. |

|
 |
|

|
External Leak - A slow leak over
years at the packing gland for a top mounted valve produced devastating losses
at this domestic hot water tank. The insulation provided some concealment for
the problem, but eventually deteriorated completely.
A failure to
address this corrosion problem resulted in significantly greater wall
loss. |
|
Deep Cratering - Severe pitting of
this water storage tank was revealed during a general ultrasonic examination.
Produced due to an external leak which was not addressed for many years, this
tank showed up to 80% deterioration in this localized area.
Welding a
secondary containment plate over this localized area was recommended. |

|
 |
|

|
Insulation Failure - A combination
of thin 1 in. fiberglass insulation, high humidity, no vapor barrier, and cold
chill water supply temperatures produced severe pitting at this pipe surface.
Removal of the exterior rust revealed heavy overall wall loss with deep
pitting of up to 0.050 in. Such conditions can only be addressed by thoroughly
removing the rust and applying an effective coating prior to
re-insulation. |
|
Inside vs. Outside - These chill
water pipe cutouts provide an ideal comparison of interior and exterior
corrosion. At the left we can see the exterior surface having been pitted due
to a failure of the fiberglass insulation.
At the right shows the
interior surface covered with a light coating of iron oxide. Overall wall
thickness is acceptable, and a comparison of inside and outside surface
conditions shows that the effect of exterior corrosion has been the major
deteriorating factor. |

|
 |
|

|
Deep Pitting - Exterior corrosion
is often at random, and will heavily attack steel pipe in one area, to the
exclusion of the rest. Typically, there is no clear reason for the localized
attack, as demonstrated by the vertical pipe example.
The removal of the
exterior rust in this sample showed generally mild corrosion attack except
along one vertical plane. In the area shown above, surface micrometer
measurements found deep channels of wall loss of up to 0.075 in. |
|
Minor Wall Loss - Looks can always
be deceiving where external pipe rust is concerned. While it does strongly
suggest a threat, a covering of rust may, in fact, only present a cosmetic
concern. Actual loss is often related to the inherent corrosion resistance of
the steel.
At the above example, removing the rust coating only produced
a very minor degree of pitting and no significant wall loss. Nevertheless, all
exterior rust should be addressed as a serious potential threat. |
|


|

The first step
toward protecting against outer pipe wall corrosion is to find out if it
exists, and to what extent - a step requiring some investigative effort.
Recommended prime locations to remove samples of insulation for inspection are
high humidity areas such as steam rooms, shaftways, mechanical rooms, open
areas, and rooftop or other locations exposed to the elements. In many
examples, water will migrate through the insulation to produce a noticeable
watermark stain or crystallization at the surface.
Supply side piping should be checked
first. Hard shell older style insulation, or insulation which is hand formed of
plaster or similar materials is usually very effective at holding back any
moisture from penetrating, and is especially effective for small diameter pipe.
Standard unpainted paper or cloth covered fiberglass, on the other hand,
provides virtually no barrier to moisture, and is always a high priority
location to check. When painted, fiberglass insulation can be effective at
retarding moisture penetration - this depending upon the composition of the
coating and its mil thickness. A single coat of paint is generally not
sufficient.
Old style cork insulation,
still in use from years ago at the oldest building properties, actually
attracts moisture, and has been shown to cause the most severe cases of outer
pipe corrosion we have seen.
While foam
type piping insulation is convenient to apply, it too has been shown to fail in
preventing the migration of moisture to the pipe surface. Painting foam
insulation is generally not an option. In addition, a recognized chemical
reaction between the components of the foam and the pipe itself has been cited
in the literature as greatly accelerating pipe surface corrosion.
Broken, missing, crushed and other
damaged sections of insulation will obviously lead to outer pipe corrosion
problems, and should be repaired or replaced as soon as it is discovered.
Missing insulation can be frequently found at transitions through walls and
floors, or in areas of heavy traffic.

A high amount of
outer corrosion can be typically found at smaller diameter pipe simply due to
the inherent difficulty of insulating its many elbows, tees, valves, strainers,
and other small piping components. Unfortunately, it is also that smaller
diameter piping which has a thinner initial wall, and which is substantially
weakened by the amount of metal cut away during the threading process. Small
diameter pipe requires little outer corrosion, therefore, to create a failure
condition. See Technical Bulletin
# P-1 about the effect of wall loss in threaded
applications.
Our standard
recommendation to ensure against moisture caused outer pipe corrosion is to
install 2 in. or heavier fiberglass pipe insulation on all cold water pipe of
50 º F. and below. In addition, a high solids paint, epoxy coating, or
hard shell outer covering, sealed thoroughly at all seams, is critically
important in order to resist moisture penetration.
Since the surface of the pipe which is
insulated is never seen, it is almost never painted. As a result, any moisture
which may accumulate at the pipe surface is able to attack completely
unprotected steel. As a precaution against such possibility, CVI recommends
painting all cold water piping with a strong rust preventative coating prior to
being insulated. This is a very worthwhile precaution to specify in any new
piping construction if long term and trouble free operation is desired.

The following
list offers some worthwhile recommendations for providing the maximum heat
transfer efficiency and condensation protection of any insulated chill or cold
water piping system:
- Install heavier
installation. Piping specifications generally require 1 thick insulation
for 12 inch black pipe chill/cold water systems at 70% relative humidity. At
80% relative humidity, 2 thick insulation is specified. Consult your
insulation supplier or contractor. Consider the humidity conditions of the area
the pipe will travel through.
- Maintain a good
moisture barrier at the outer pipe surface. Require smooth seals and joints
throughout the entire installation in order to prevent moisture penetration.
Stapled insulation, without being sealed, is a prime cause of insulation
failure.
- Install a
secondary metal, PVC, or other hard vinyl outer jacketing over the existing
insulation. Overlap and seal the adjoining sections using a bead of silicone or
other waterproof adhesive.
- Protect all
insulation from physical damage. Provide steps and bridges over insulation in
high traffic areas. Caution staff against standing on insulated pipe. Repair
all cuts and rips in the insulation immediately.
- Apply an
isolating seal of mastic or other waterproofing material at regular intervals
between sections of insulation. This is especially important for outdoor
locations. Should a breakdown at a particular area of insulation occur for any
reason, the resulting condensation and water will be prevented from migrating
throughout the adjoining insulation and piping.
- Apply a good
quality rust preventative coating to the base piping as soon as it is in place,
and prior to insulating. Paint around the entire pipe circumference.
- Migrating Vapor
Corrosion Inhibitors (VCI) may be applicable to retard corrosion at already
insulated piping which is known to have a corrosion problem, and cannot be
immediately addressed.
- Paint the
insulation immediately after it is installed as a moisture barrier. A initial
heavy coating of paint will penetrate the semi-permeable cloth or paper
covering of the insulation to further protect against moisture migration.
Require that the entire circumference of all piping is covered in order to seal
the entire surface.
- Insulated
piping located outside exists under even greater threat from insulation failure
due to varying environmental conditions. This places even more importance upon
the above recommendations.

Some latest
nondestructive testing technology does exist that can scan through piping
insulation quickly and effectively to identify any hidden corrosion problem.
This is best to contract as a service, and is an extremely cost effective means
to safeguard against the above problems. Other sensing devices can detect
waterlogged insulation and rust deposits at both the inside and outside of the
pipe.
CorrView International recommends
these and any other preventative measures as a means to avoid this devastating
but very avoidable operating problem.
©
Copyright
|
|
|
|
|
|
|

|
|
|
 |
|
|