Line


     Installing a water filter for any larger piping system is often a capitol decision costing $25,000 or more. In most cases, it is in direct response to a recognized corrosion problem - where its function may play an even greater role in protecting millions of dollars of equipment, product, revenue, or infrastructure.

     What often occurs, however, is that the filter removes a certain volume of dirt and particulates within its first few weeks of being installed, but then slows dramatically in its backwashing cycle or cleaning frequency. This change is sometimes interpreted incorrectly as either a failure of the unit's operation or design, but more likely - that the corrosion problem has been resolved. The filter installation is viewed as a total success, and the problem is forgotten.

     In many cases, a filtration unit, and especially a high efficiency sand filter or basket/bag housing type filter, will clean up the fine suspended particulates and turbidity of the water to produce a noticeable improvement in clarity, color, and appearance. This improved water quality, in turn, is perceived as an improvement in removing deposits from the piping also - which is very rarely the case. See Technical Bulletin M-10 regarding the difference between clean water and clean pipe.

     First suspicion is always that the filtering unit is not functioning correctly. Closer inspection and trouble shooting, however, will typically verify the unit's proper operation - to leave further questions remaining. In fact, the problem actually rests in two areas:


     First is the chemical treatment program. Since years of operation may have deposited hundreds and perhaps thousands of pounds of iron oxide corrosion product at the interior piping surface prior to the filter unit being installed, it is impossible to remove those deposits using filtration alone, and in only a few weeks or months, possibly even years. Deposits are usually hardened in place and will resist most mild detergent cleaners. See Technical Bulletin C-1 regarding the volume of corrosion product created at different corrosion rates.

     Every filtration system therefore requires supplemental chemical agents to loosen and re-suspend the attached deposits back into the water flow and maintain it moving in circulation. Ideally, efforts to re-suspend the particulates into the water flow should be effective, but not exceed the reasonable capture rate of the filter.

     A review of all options with the water treatment contractor should help in choosing a safe but effective chemical capable of loosening the deposits and maintaining them suspended in solution. Removing a sample of deposit laden pipe for lab analysis is almost mandatory. A laboratory trial cleaning of the proposed chemical against those same pipe deposits will even better demonstrate the likely degree of success, and potential damage caused to the pipe itself.

     Above all, CVI recommends avoiding any strong acid or alkali cleaners except where thorough ultrasonic and nondestructive testing has been performed to identify any weakened areas of pipe, joints, A/C units, etc. Corrosion coupons of both steel and copper are especially important during any cleaning procedure in order to monitor for an increase in wall loss.


     A second and possibly more important reason for a low efficiency problem is the filter installation itself, since very often, the piping layout to the filter or its location will dramatically reduce its effectiveness.

     This is not a concern for full flow filtration units since they must, by definition, be in line. Still, full flow filters are most effective if located on the supply riser downfeed from the cooling tower, and should ideally be located at the very bottom of the system.


Critically important to all filter installations are the basic laws of physics and inertia, and the fact that particles have the interest to continue their travel in a straight line relative to their mass.

Very light particles are more likely to change direction and move with the water flow, while heavier particles and larger chips of iron oxide and scale, for example, are more likely to continue in a straight line.


     For side stream filtration, the actual location of the filter is far more important - with placement of the take-off inlet line greatly influencing its capture efficiency. Most often, side stream units are installed across the suction and discharge headers of the pumps in order to utilize their 40-80 PSI differential to move the water through the filter. Since almost all pumps have coarse strainers at their inlets, larger particulates are captured there, or shattered into smaller particulates for re-suspension into the system.


     In such cases, the take-off connections to and from the filter are typically oriented perpendicular to the flow of water, and at either 3 or 9 o'clock positions for horizontal lines - and sometimes even at 12 o'clock. This side take-off arrangement assumes that any suspended particulates will literally stop dead and change direction 90 degrees at the point of highest velocity within the entire piping system - an impossible event.

     Virtually no large particulates are likely to reach the filter under such conditions, and will instead travel straight past the filter inlet to settle in some other lower flow area of the system prior to ever being captured. Furthermore, many circulating pumps are not located at the absolute bottom of the piping system, where the concentration of particulates is usually the greatest.

     Water flow in the area of a pump header will be quite turbulent, and therefore provide slight benefit by randomly forcing larger particles into the filter inlet. However, if the filter take-off is connected after an extended horizontal run, the water flow may become more laminar, and thereby concentrate particulates at the center and bottom of the pipe - again away from any side oriented filter inlet.


     From our extensive involvement in ultrasonic pipe testing, we have well documented the volume of iron oxide and other particulate deposits which commonly accumulates in condenser water and other HVAC piping systems. Given even a low corrosion rate of 1-2 mils per year, hundreds and possibly thousands of pounds of rust deposits can accumulate over one or two decades, and will remain attached to the pipe without some mechanism to remove them. A not uncommon 20% loss of wall thickness at 12 in. Schedule 40 condenser water pipe actually means that 10.7 lbs. of steel has been lost per every linear foot. See Technical Bulletin # C-1 for the actual pounds of metal lost and deposits created at various corrosion rates.

     For an 800 ft. riser system, that same 20% thickness loss means that approximately 8,560 lbs. of steel has been oxidized and transformed into a less dense mass of iron oxide having approximately 18 times its original volume. And now, some percentage of that volume will still exist within the piping system to cause further deterioration.See Technical Bulletin C-4 about the problems associated with interior deposits.

     Any expectation of removing such internal corrosion, or even a small proportion of it through the use of a side take-off intake to any by-pass filter, is virtually impossible. At most, such an installation will only provide the most minimal removal of the smallest suspended particulates, leaving the overwhelming balance behind. An improperly installed filtration unit will not even keep up with the rate of new rust deposits naturally cerated.

     Were the removal of such a high volume of debris, scale, rust, and other particulates successful, new problems would be created at the drain lines where the backwash was directed. Our experience has shown it rare for any automatic filter installation to include a settling tank to collect the backwashed deposits, with almost all backwash lines piped directly to drain. Yet, clogged floor drains and sumps, which would occur if hundreds of pounds of rust deposits were directly discharged into them, rarely, if ever occur.

     In one way, piping the backwash directly to drain eliminates any evidence of filter efficiency, but by definition of not creating drain line problems, defines that the filter is not as effective as likely planned. The below photo, taken of an automatic side stream filter installation having a collection and settling tank for backwash deposits, is a prime example.

     Seen from a downward inside view, this 3 ft. diameter x 4 ft. high tank had collected so few deposits that not even the entire bottom of the settling tank was covered. The filter, one of the most efffective automatic units on the market, removed perhaps only 1 lb. of rust in over 18 months of 24 hour/day operation of an open condenser water system known to be heavy with particulates.

     Given that the supply and return distribution piping removed from the system were found clogged almost 50% with interior deposits, and that thousands of pounts of particulates were known to exist throughout the 36 floor office property, this investment in filtration was shown to be virtually worthless. The purchase of one of the best automatic filters on the market, installed at a 2 in. perpendicular take-off to a 18 in. vertical supply riser, ultimately accomplished nothing.



     A much better alternative is to install the filter at the very bottom of the supply line from the cooling tower, or at the bottom of the downfeed line in the case of a closed system. This uses gravity to advantage in not only directing the particulates downward, but with increased force. With a higher system pressure normally found at the return piping upward, this configuration requires a supplemental circulating pump at additional installation, energy, and maintenance costs.

     The piping layout is critical in itself. Whenever possible, the filter inlet should be in a straight and downward direction from either the cooling tower or closed system downfeed piping. This takes advantage of the inertial forces which tend to move all particulates in a straight line whenever the water changes direction. If possible, we recommend replacing a basement or lowest level downfeed elbow with a full size tee instead, and then reducing the tee diameter to the size of the filter pipe inlet.

     Extending the bottom of the tee piping in its original dimension approximately 3-4 ft. provides a collection chamber or dead leg, and even further improvement to filtering efficiency. Expanding this same collection piping to a greater diameter, 6 in. to 24 in. for example, immediately drops the water velocity at this end point - thereby producing greater settling and even more filtration benefit at relatively low cost.

     The layout of the piping is also a major factor. Where low flows and/or long horizontal runs exist, particulates, even if they are loosened by the action of a chemical agent, may not migrate back into the main flow stream to be picked up by the filtering device. The most effective and sophisticated filtering device becomes virtually useless if insufficient flow exists to move the particulates to its collection inlet. Therefore checking flow velocity is always important to secure whether booster pumps may be needed.


     In our experience, we rarely find filtering systems installed to provide maximum effectiveness, nor a chemical treatment program even addressing the question of existing interior deposits. Normally, after spending $25,000 or more on the filtration unit, corners are usually cut to reduce installation and operating costs, and only a small degree of benefit is realized as a result.

     While the selection of the filtering device itself is a priority concern, CVI recommends providing an equal amount of attention to its placement, installation, and chemical treatment program. A realistic assessment of pipe quality, volume of deposits, and threat level to the system are also important areas to consider - meaning that ultrasonic and metallurgical testing are a must.

     Combined, the proper combination of planning and engineering can turn an otherwise mediocre performing water filter into a unit that makes substantial improvement to building or plant operations.


Review our disclaimer on any technical information contained within this Internet site.


©  Copyright