| |
|
 |
|
 |
|
|
|

|


Comparison
testing was performed to measure the relative corrosion rate of the most
commonly used CorrView ® model in 1-1/2 in. ASTM 1018
steel, and the most commonly installed pipe for HVAC and process water systems
- ASTM A53. Testing was performed under water immersion.

A 1-1/2 in. size
standard CorrView ® corrosion monitor manufactured of
ASTM 1018 mild steel was installed into a test assembly comprised of a 3 in.
threaded length of ASTM A53 pipe via a 3 x 1-1/2 reducing adaptor. The outer
surface of the 3 in. length of pipe was sanded smooth to minimize any error
during ultrasonic testing, and to provide a reliable bonding surface.
An EPDM rubber template having die cut
holes precisely matching the ultrasonic probe diameter was bonded onto the pipe
using Loctite metal to rubber bonding adhesive - thereby ensuring precice
re-orientation of the UT probe on subsequent evaluation. Duct tape was used to
hold the template in place while the adhesive cured.
 |
|
| Side View Of Test
Assembly |
|
 |
|
| Close-Up View Of Testing
Template |
Following a
specialized UT testing procedure developed by CVI for using a client's existing
pipe as an "ultimate corrosion coupon," repetitive wall thickness
measurements and recalibration were performed until three individal
measurements produced the same wall thickness value. A total of 15 sets of such
precise wall thickness measurements were taken along two separate templates on
the pipe, and recorded in a spreadsheet to provide a
baseline.
In addition, 15 wall thickness
measurements were performed in a close circular pattern at the innermost 3/8
in. diameter of the front wear surface of CorrView ® and
similarly recorded.

The test
assembly was placed on its closed end and filled with city water. Muriatic acid
was added to reduce the pH of the water to approximately 5. Aeration of the
solution was added, and the test assembly allowed to remain for a period of
time under ambient conditions. Subsequent testing would measure the wall loss
of the interior surface of the pipe against the exterior surface of CorrView
® - both surfaces being subject to essentially identical
corrosive conditions.

Following 39
days of continuous and undisturbed immersion, the solution of rusty water was
drained and CorrView ® removed for re-testing. Ultrasonic
thickness measurement was again performed along the same 15 template points,
and at the front surface of CorrView ®.
The 15 test locations along the ASTM A53
pipe showed a wall loss of between 0.000 in. and 0.002 in., for a calculated
average loss of 0.000786 in. or 0.786 thousands. Calculating the wall loss over
time it was exposed to the corrosive environment produced a corrosion rate
estimate of 7.35 mils per year. Measurement at the same area of CorrView
® front wear surface produced a wall loss of between 0.000
in. and 0.001 in., for an average thickness measurement of 0.000999 in. or
0.999 thousands. Calculating this wall loss over exposure time then produced an
estimated corrosion rate of 9.36 mils per
year.
This represents an approximate 20%
difference in reported corrosion rates between CorrView ®
and actual ASTM A53 pipe under identical conditions. We consider such results
excellent considering that the difference in true pipe corrosion rate and
corrosion coupons are often in error by 10 times or 1,000 percent or more. This
is not due to any failure of the corrosion coupons themselves, but due to their
placement in an isolated loop where the many other corrosive factors affecting
the pipe are excluded from the testing
procedure.
This same testing assembly is
currently undergoing exposure for an additional 60 days. |
|
|
|
|
|

|
|
|
 |
|
|