PI-06:   A Hidden Threat The Severe And Hidden Danger To any Condenser Water Piping System Which Is Annually Drained Down There is a general understanding by those working within the building operations, plant engineering, and water treatment fields that drained carbon steel pipe will corrode to a higher degree than pipe which is always filled with water.  This produces a tremendous vulnerability to the piping system, and one which is typically hidden from view. While the actual degree of wall loss for drained pipe is in most cases undefined and only speculated upon, a presumption that it does exist often prompts preventative action.  For those responsible for the operation of building or plant properties in Northern sub-freezing climates, freeze protection for less than 24/7 operations is required – thereby introducing new corrosion concerns as well. Corrosion Activity Varies Such wall loss varies greatly, and is, unfortunately, far from being predictable.  Pipe which is drained and left in a wet condition has been documented to corrode at as much as 10 or more times the rate of pipe left filled with…

Loading

Read More

CT-10:   Corrosion’s Greater Impact To Chill Water Pipe Specific Causes Leading to Interior and Exterior Corrosion of Chill Water Piping Pipe corrosion represents the 2nd greatest threat to any building property next only to fire.  Different levels of threat exist for different piping systems – a roof level pinhole leak at a condenser water line representing a far lesser threat than a chill water pipe separation over high voltage electrical switchgear equipment.  Failures resulting from the corrosion of piping systems are easily capable of producing millions of dollars in equipment and water damage for most building properties, are cited at $1 million dollars of lost trading revenue per minute for a financial institution’s data center, and has caused the loss of human life where rust corrosion product itself has stopped water flow through a fire sprinkler system. Corrosion Is A Natural And Unstoppable Force Of Nature Simply stated, corrosion is the natural reversion of certain metals back into their original elements over time.  It can be slowed and greatly reduced by precautionary measures such as the addition of chemical corrosion…

Loading

Read More

CT-09:   Dual Temperature Piping Multiple Negative Factors Which Define Its Overall Greater Vulnerability Of the various piping systems subject to corrosion under insulation, CUI, dual temperature heating and cooling systems have consistently shown the greatest vulnerability.  In contrast to many other colder temperature piping systems, a combination of multiple factors exist.  Below we itemize the top 11 issues contributing to their higher failure potential:   1. First and foremost is the generally smaller diameter pipe installed at multiple risers. Existing at 4 in. and smaller, this pipe is typically threaded in its construction and therefore suffers an immediate near 50% wall loss at the thread cut. 2. The design of dual temperature piping systems is fairly typical throughout the HVAC industry and across the United States.  Almost all such systems are installed with risers at its perimeter support columns in order to feed the below window fan units – placing the pipe into a higher humidity environment.  Moisture can and will penetrate the outer building envelop to ultimately reach pipe which is poorly protected from its effects. 3. Most dual temperature piping systems are reduced reverse…

Loading

Read More

CT-08:   Localized Corrosion Issues Corrosion Trends In New York City Building Properties The corrosion of steel piping and its related components are a continuous and virtually unstoppable process.  Only fire presents a more potentially damaging threat to the operation of a commercial building.  In its less serious form, corrosion can produce problems ranging from lost heat transfer efficiency and constricted pipes – to annoyance pinhole leaks and temporary shutdowns. In extreme, but all too common examples, the failure to recognize and address a serious corrosion problem often results in a major pipe failure, loss of system services, high replacement costs, and legal liability.  For New York City properties, the age of the structure has a significant impact regarding pipe condition due to the various changes in construction and materials which have taken place over many decades. The age of a building property often defines the grade of pipe material used, it’s schedule or beginning wall thickness, corrosion susceptibility, and the general conditions under which natural deterioration has taken place.  Having provided piping evaluations at hundreds of commercial building properties throughout New York, we find that most piping systems can…

Loading

Read More

CT-07:   External Pipe Corrosion The Hidden Threat To Every Chill And Cold Water Piping System Throughout the history of most building properties and plant operations, some degree of corrosion at the external surface of the chill and cold water piping will occur.  Surface pipe corrosion can range from cosmetic and mild, to severe and system debilitating.  Corrosion under insulation, CUI as it is known, is generally a long term problem taking decades to develop.  This partially explains its low priority in most building and plant maintenance plans and procedures. The presence of condensation at the outer pipe wall produces much the same corrosive effects typically associated with interior pipe corrosion, except that microbiological attack rarely occurs.  In extreme cases, condensation will build up to the point where the insulation becomes completely saturated with water.  Generalized corrosion, excessive surface pitting, as well as the deterioration and failure of the insulation itself, usually results. Although presumed to be a long term problem, under certain conditions, exterior corrosion can produce a noticeable impact within 10 years. Cold Insulation Of Secondary Importance While fiberglass, foam, and other forms…

Loading

Read More

CT-06:   Piping Problems The Six Most Common Forms Of Corrosion Affecting HVAC And Process Piping Systems While the external signs can sometimes be subtle, learning of a corrosion problem often requires little more than a quick look into the cooling tower pans or related HVAC equipment such as refrigeration machines, pumps, and heat exchangers.  A rust build-up at the tower, fouled drift eliminators, tuberculation deposits, and flakes of scale and rust caught in the condenser water tubes are obvious indications of a corrosion problem.  Likewise, encrustations at the threaded joints, buckets of rust captured at start-up, a 10 MPY corrosion coupon result, lost heat transfer, and failed equipment should prompt the need to investigate further. Under real world conditions defined by the laws of nature, some degree of corrosion must be expected to exist within any piping system.  However, identifying the type and severity of corrosion responsible requires far more effort, and often multiple investigative tools.  The monitoring, testing, diagnosis, control, and repair of piping related corrosion problems is a multi-billion dollar business in itself.  Yet, corrosion caused piping replacement in the United States still exceeds…

Loading

Read More

CT-01:   Inadequate Corrosion Control Recognizing The True Threat Of Corrosion To Building Services Piping The severe corrosion of HVAC piping systems and their related equipment presents the most potentially damaging losses to any private, government, industrial, or commercial property next only to the threat of fire. It is surprising to see, therefore, the relatively low priority often provided for corrosion control and monitoring of critical HVAC and process piping by many building owners, operators, and plant engineers.  For many building properties, corrosion control is of little concern.  Whereas condenser and open water corrosion rates of 0.5 – 2 mils per year (MPY) were typical only three decades ago and easy to achieve, it is now common to find system-wide corrosion rates of 5 MPY and greater – with rates occasionally as high as 30 MPY. While certain unavoidable factors have contributed to generally higher corrosion rates, it remains clear that the service life of most piping systems could be greatly extended by allocating further effort to corrosion control measures. Massive Reporting Error A major factor in many pipe failures we see is caused by the often…

Loading

Read More

CM-03:   Someone To Blame Reducing Your Legal Liability By Actively Monitoring For Corrosion Activity The corrosion of HVAC piping systems and their related equipment presents the most potentially damaging losses to any private, industrial or commercial property next to the threat of fire.  Direct losses exist in pipe repair and replacement costs, but often the most far reaching losses are in the form of litigation due to water/property damage and lost productivity.  Some of the most damaging pipe failures we are aware of have shut down entire high rise office buildings, or caused extensive damage to multiple floors of tenant space. Where a building property has the responsibility of providing basic heating and cooling services as part of their lease contract, the failure of any large and pressurized piping system, especially where significant water damage is concerned, means a very expensive repair and damages bill for those responsible. Chemical Treatment No Guarantee Methods to minimize corrosion and monitor its severity exist, but do not necessarily guarantee trouble free service.  Corrosion caused leaks can occur even though top quality water treatment is provided,…

Loading

Read More

CM-02:   Extending Service Life Evidence That Good Corrosion Control Is Possible By Following Certain Guidelines Pipe corrosion is a major problem for building and industrial properties, and totals billions of dollars in losses for the United States alone.  Our new corrosion monitor CorrView ®, as well as our ultrasonic testing services and the majority of this website, is focused toward the monitoring and remediation of corrosion related problems. As the content of our website clearly illustrates, corrosion is a significant threat to any building operation, and can produce problems ranging from mild annoyance and small repairs, to major failures and millions of dollars in damage and replacement costs.  Such corrosion problems seem to be on the increase for virtually all piping systems. Proper Planning Necessary Most corrosion problems begin before the water ever enters the pipe, and advanced planning is a key element to a long running and properly operating piping system.  Appropriate filtration to an open or closed cooling system is today a necessity, rather than an option.  A well planned and executed chemical treatment program including fully automatic feeding equipment…

Loading

Read More

CP-04:   Closed Piping System Corrosion Avoiding A Problem That Should Never Occur Of the many corrosion problems that plague a typical building property, corrosion at a closed HVAC piping system should never occur. Fundamentally, corrosion impacts different piping systems in different forms and at widely varying rates.  Other than protective coatings or pipe lining, little can be done to control corrosion activity at plumbing, sanitary waste, and domestic water systems.  Some options are available for fire sprinkler lines but rarely employed. Dry fire sprinkler systems experience far greater and more advanced failures than wet systems.  Steam systems are less impacted with very uniform wall loss; while steam condensate lines always suffer greater corrosion threat due to deep pitting.  Condenser water service typically requires the closest attention and highest chemical cost expenditure, with results widely dependent upon many different factors. For many piping systems, layout, design, corrosion protection ,filtration, and especially materials of installation will play a significant role in its future service. For a closed piping system such as hot water heating, secondary, closed condenser water, chill water, dual temperature, reheat, or other service,…